Safety, Instrument & Vital Power Systems - 125 V DC Systems AND 120 V Instrument AC Systems Flashcards
Discuss the 125VDC function.
Supplies 125 VDC to various control and instrumentation circuits and to DC operated equipment.
State the purposes of the Battery.
Provide a backup source of power to the DC bus if the associated battery charger fails
Rating - 2400 amp*hr @ 8 hour discharge rate (4 hour emergency period)
What is the Battery/Battery Charger Interlock, (A and B DC buses only)?
Mechanical bar interlock
Prevents the Battery / DC bus breaker and the Load Bank breaker from both being closed
What are the DC Bus Interlocks?
UV trip between safety buses (outer tie bkr trips inner tie bkr on UV for AB bus)
2 keys for the 4 safety bus tie bkrs
Admin control of C/AB and D/AB bkr keys
Discuss the Battery Chargers.
Supplies trickle (Float) charge to the batteries at 132-135 VDC,
315 amps Max, Warm up time 15 minutes
Equipped with variable timer up to 24 hours for an Equalize charge 137 VDC – No Alarm
156 VDC – Hi Volt Shutdown Relay will trip the Charger Output Breaker. Must be reset inside the cabinet.
136-137.5 VDC – When in Equalizing mode
138-140 VDC - Hi Volt Alarm,
129 VDC - Min TS voltage while in FLOAT,
Low voltage ALARM @ 109 Volts!!! - Tech Spec violation before alarm comes in.
Discuss the Battery Charger Ground Test.
3 position switch – POS GND / Normal / NEG GND
The positive or negative light burns dimly when it is selected.
The control room gets a ground alarm when tested.
If a large CHGR ground develops, you get a CR ground alarm & ground light on the charger turns on
With an actual ground on the charger, placing the ground test switch to positive and negative positions will show a difference in brightness. The side with the brightest light has the ground.
When performing the Battery Charger Ground Test, what is the indication as to which side has the ground?
The side with the brightest light has the ground.
Discuss Placing a Battery Charger in-service.
Close MCC feeder bkr to BC,
Place On/Off switch to on
Close AC input bkr, wait 15 min. – Why wait 15 minutes? Failure to warm up charger prior to being put into service may cause charger to trip
Close DC output bkr
Verify 132-137 VDC,
Close BC bkr to bus
Verify system response
Discuss Removing a Battery Charger from Service.
Check system status
Open BC feeder bkr to bus
Verify system response
Place On/Off switch to off
Open AC input bkr
Open DC output bkr
Open MCC feeder bkr to BC
Discuss why the 125 VDC Buses Are Ungrounded.
This means that it takes 2 grounds to cause excessive current flow that will damage the Bus.
First Ground can be detected by a Hi Voltage reading on the Bus Ground Detector
Discuss the DC Bus Ground Test Device.
“OFF” and “Ground Test” with spring return to “OFF
Bottom line: on bus ground detection, the DIMMEST side has the ground
Discuss how to Swap AB DC Bus Power Supplies.
Live bus transfer, the AB charger is placed in-service prior to swapping
AB Battery Charger is normally maintained in Standby Mode – Know what this is
Take AB BC to equalize mode
Close AB BC feeder bkr to bus (live bus transfer)
Verify system response
Open inner tie bkr
Open outer tie bkr
Close other outer tie bkr
Close other inner tie bkr
Take AB BC to Normal mode (float)
Open AB BC feeder bkr to bus
Discuss the effects of a Loss of DC bus.
2/4 RPS channels de-energize = Rx trip
2/4 ESFAS channels de-energize = ESFAS actuation (except RAS, CSAS, DSS which are energize to actuate)
1 AFAS channel in trip, 1 AFAS channel in bypass (More detail in AFW / AFAS notes)
Loss of breaker control power
{Loss of AB DC Bus on U1 results in 1C AFW inoperability – 10 min action to swap AB dc bus to energized bus}
What are the Unit 1 Battery Charger Power Supplies?
Battery Charger/MCC
A A5
AA A6
B B5
BB B6
AB AB
C A1
D B1
What are the Unit 2 Battery Charger Power Supplies?
Battery Charger/MCC
A A5
AA A5 **
B B5
BB B5 **
AB AB
C C
D C
** - Significance of this means that a loss of the A5 (or B5) MCC on Unit 2 results in the loss of both Battery Chargers to the A (or B) DC bus – 2 hour action required by T/S’s