Main Power Distribution Flashcards
Per 0-AOP-53.04 Reduced Offsite Transmission Capacity, what must be done if only one transmission line is available and BOTH units are online? (include time limit)
One unit is required to be tripped within 4 minutes
Per 0-AOP-53.04 Reduced Offsite Transmission Capacity, why must one unit be tripped within 4 minutes if only one transmission line is available?
Failure or delay in tripping the selected unit with two units on-line with one transmission line in service beyond the values specified in 0-AOP-53.04 Attachment 1, (4 minutes) may result in a LOOP and permanent damage to the transmission line.
What is min/max switchyard voltage with no SUTs in service?
Low limit - 230KV, High Limit - 244 KV
Low operability limit does not apply in Modes 5 & 6 because the unit load is minimal and a valid SIAS is not considered credible.
What is min/max switchyard voltage with SUTs in service?
Low limit - 230KV, High Limit - 241 KV
Low operability limit does not apply in Modes 5 & 6 because the unit load is minimal and a valid SIAS is not considered credible.
Per 0-AOP-53.02, Low SWYD Voltage, what actions are required with switchyard voltage <230KV?
- Both offsite sources (SUT’s) are declared inoperable
- Refer to T/S 3.8.1 for required actions – shutdown required if not corrected w/in 24 hours
- NRC notification required w/in 8 hours per LI-AA-102-1001, Regulatory Reporting
Per 0-AOP-53.03, High SWYD Voltage, what actions are required with switchyard voltage greater than limits?
- Ensure Main Generator is operating w/in the limits of the Generator Capability Curves
- Contact System to coordinate reducing VARS to lower switchyard voltage
- Monitor 6900V, 4160V and 480V bus voltages. Monitor for equipment damage.
State the loads powered from A1 and B1 buses.
MFW pumps, RCPs
State the non-safety related 4160V buses.
A2, B2
State the safety related 4160V buses.
A3, B3, AB
State the non-safety related 480V load centers.
A1, B1
State the safety related 480V load centers.
A2, B2 [A2, A5, B2, B5]
State the Unit 1 non-safety related MCCs.
A1, A2, A3, A4,
B1, B2, B3, B4, B10
B9 (SGBTF U1 feed)
1C
State the Unit 2 non-safety related MCCs.
A1, A2, A3, A10, A11,
B1, B2, B3, B10
B9 (SGBTF Unit 2 Feed)
2C
State the safety related MCCs.
A5, A6, A7, A8,
B5, B6, B7, B8,
AB
What supplies control power to 1A1 and 1B1 busses?
1A1 - 125V DC Bus ‘A’
1B1 - 125V DC Bus ‘B’
What supplies control power to 2A1 and 2B1 busses?
2A1 - 125V DC Bus ‘A’
2B1 - 125V DC Bus ‘B’
Note ** - SU XFMR Feeder Breakers to 6.9 KV Buses are opposite train powered
2A SUT feeder to 6.9 KV Bus 2A1 - 125V DC Bus ‘B’
2B SUT feeder to 6.9 KV Bus 2B1 - 125V DC Bus ‘A’
What supplies control power to 1[2]A2/B2 busses?
1[2]A2 - 125V DC Bus ‘A’
1[2]B2 - 125V DC Bus ‘B’
What supplies control power to 1[2]A3/1[2]B3 busses?
1[2]A3 - 125V DC Bus ‘A’
1[2]B3 - 125V DC Bus ‘B’
What supplies control power to 2A4/2B4 busses?
2A4 - 125V DC Bus ‘1C’ OR ‘2C’
2B4 - 125V DC Bus ‘1C’ OR ‘2C’
What supplies control power to 480V Load Centers?
All ‘A’ Train - 125V DC Bus ‘A’
All ‘B’ Train - 125V DC Bus ‘B’
1[2]AB - 125V DC Bus ‘AB’