Relief Valve Flashcards
For pumps from 1,250 to 2,250 GPM, how many inches (size) is the relief valve?
3 to 4
The Waterhouse relief valve is ___ separate units.
1.
2.
2
Relief valve proper (the muscle that relieves)
Pilot valve (controls the proper)
When setting the relief valve, turn valve what direction until the main gauge drops 5 to 10 psi.
Counter clockwise
When a relief valve is acting sluggish or how after shall you excessive valve?
Monthly
What controls the Relief Valve Proper?
Pilot Valve
To set the relief valve, slowly turn pressure control knob counter-clockwise until main gage PSI drops ______ PSI below desired setting & ambler light illuminates.
5 to 10
What happens if you open the relief valve drain when the fire pump is operating?
PSI decreases
What PSI is the relief valve lowest setting?
70
What shall you do with the relief valve when PSI is above 300 psi ?
Turn system off
The relief valve must have ___ PSI pressure differential between intake and discharge pressure?
50 psi
What is the max setting?
300 psi
The Relief Valve is equipped with indicator lights.
A green light means valve is :
An amber light means valve is :
Green-closed
Amber-partially or fully open
Engage pump and increase discharge pressure to 150 psi at least ______.
Monthly