Radwaste Building HVAC Flashcards

0
Q

How is smoke removal accomplished in the Radwaste building?

A

Fire and smoke detectors alarm in the control room; smoke is removed by exhaust AFUs and supplemented by portable smoke ejectors.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
1
Q

State the function of Radwaste building HVAC

A

1) maintains temps within limits during normal plant operating and shutdown conditions.
2) provide ventilation air to Radwaste building
3) minimize airborne radioactivity release with a negative building pressure
4) monitor and filter exhaust air discharged out the plant vent stack

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What components in the GR system vent to the HR system?

A

1) release path discharges upstream of the AFUs
2) waste gas surge tank relief valve
3) GR compressor pre-filter
4) GR compressor suction filter
5) GR compressor package

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What LR system components vent to the HR system?

A

1) LR system evaporator surface condenser and heater
2) concentrate monitor tanks
3) LR holdup tanks

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What happens to the HR system on a loss of IA?

A

Dampers fail closed and AHUs and AFUs trip on overload

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Where does the Radwaste building HVAC system discharge to?

A

Plant vent

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What components makeup the RW control room normal AHU?

A

Moderate efficiency air filter, chilled water cooling coil, fan, and an electric heater

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

At what temperature does the rad waste control room duct heater energize?

A

Supply air temperature less than 75F if the heater air flow is not low and the breaker is closed.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

How are the OSA dampers interlocked with the AHUs?

A

When the fan is running, the damper is open and when the fan is stopped, the damper is closed.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is required for an OSA AHU air washer pump to start?

A

A permissive signal from the associated running AHU fan and a signal from the intake temperature controller that the outside air temp is >80F .

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What will cause the exhaust normal AFUs to trip?

A

Receipt of an electrical protection signal

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Where does RU-14 sample from?

A

All exhaust from the rad waste building which will sound an alarm.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What does RU-15 monitor?

A

Combined exhaust from the waste gas system.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What is the sequence for starting the decon facility HVAC subsystem?

A

Place the AFU on line first, then the AHU to keep from pressurizing the building.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What happens to the RW building dampers on a loss of NK?

A

Dampers fail closed and AHUs and AFUs trip on overload.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Why is it preferred to run the AFU and AHU on the same train together?

A

To prevent positive pressurization of the Radwaste building due to loss of power to one train.