RACT Unit 25 Overview Flashcards
Mechanical Controls:
- Start, stop, or modulate fluid flow and can be operated by ________ or _________
- pressure or temperature or other means
2. piping
Evaporator Pressure Regulator (EPR):
- Prevents the pressure in an evaporator from ______ below a predetermined pressure
- Positioning controlled by ____ pressures which are ________ pressure and ______ pressure
- Also referred to as _____ on rise of ____ pressure
- Only establish a ________ pressure and do not hold a _______ pressure or limit maximum pressure
- dropping
- two, evaporator and spring pressure
- open on rise of inlet pressure valves
- minimum, do not hold a constant
Multiple Evaporator Systems:
- Single compressor with _______ evaporators
EPR Valves:
- Allow each evaporator to operate at its own ________ and __________
- Are equipped with ______ valves to allow gauge readings on the evaporator side of the valve
- Common suction-line pressure can be obtained at the compressor ________ valve
- multiple
- at its own pressure and temperature
- schrader
- service valves
Electric Evaporator Pressure-Regulating (EEPR) Valves:
- Provide more accurate _________
- Designed to maintain _______ air temperature in the refrigerated case
- Controlled by a bipolar ______ motor
Locations:
- Single evaporator: evaporator _______
- Multiple Evaporators: suction line before the common suction ________
- Control
- discharge
- bipolar stepper motor
- outlet
- suction line before the common suction header
Crankcase Pressure Regulator:
- Resembles an ____ valve
- Located close to the __________
- Keeps a low-temperature compressor from overloading during a ___ ____down
- Referred to as a ____ on rise of _____ valve
- Controlled by crankcase (outlet) pressure and its _______ pressure
- EPR
- Compressor
- during a hot pull down
- close on rise of outlet (CRO) valve
- spring pressure
Adjusting the CPR Valve:
- Should be accomplished on a hot pulldown or at least when the compressor has enough load that it is trying to run ________
- It is important to use an _______ on the compressor while adjusting the CPR valve to ensure that the amperage draw of the compressor does not exceed the full load amperage rating
- overloaded
2. ammeter
Oil Separators:
- Installed in the ________ line
- Separate oil from the refrigerant and return the oil to the compressor _________
- Oil drops fall to the bottom of the ________
- Oil level raises a float and opens a ______
- Difference between _____ and ___-side pressures push oil back to the compressor
- Another type is the ______ oil separator
- Device needs to be kept ______
- discharge line
- crankcase
- separator
- opens a valve
- high and low side
- helical oil separator
- warm
Vibration Eliminators:
- Often necessary to protect the tubing at the ______ and ________ lines
- Eliminated on small compressors successfully with _______ loops
- Large ______ requires special vibration eliminators constructed with a bellows-type lining and a flexible outer protective support
- suction and discharge lines
- vibration loops
- large tubing
Crankcase Heat:
The crankcase heater;
- Designed to help combat refrigerant ________
- Holds oil in the compressor’s crankcase at a temperature _______ than the coldest part of the system
Common in air-conditioning systems
- Can be applied in _______ ways
- Only needed (and desired) during the ____ _____
- migration
- higher
- several
- during the off-cycle
Oil Pumps:
- Larger compressors have ______ oiling systems that usually have over __ horsepower
- Contain an oil pump located at the end of the compressors _______
- Keyed into the compressors ________
- Can be of the gear or _______ type
- Squeezes the oil to a ______ pressure which is referred to as the ___ oil pressure
- forced oiling systems that usually have over 3 horsepower
- crankshaft
- crankshaft
- gear or eccentric type
- higher pressure which is referred to as the net oil pressure
Low Ambient Controls:
- Used on systems that are operated year round to maintain _____ pressure
Methods used to keep the head pressure at an acceptable level;
- Fan cycling using a _______ control
- ___ speed control
- Air volume control using ______ and fan cycling
- Condenser _______ and condenser _______
- maintain head pressure
- fan cycling using pressure control
- fan speed control
- air volume control using shutters and fan cycling
- condenser flooding and condenser splitting
Fan-Cycling Head Pressure Controls:
- Device opens on a drop in head pressure, turning condenser fan ____
- Device closes on a rise in _____ pressure, turning the condenser fan ___
- Fan cycling causes large _______ in the head pressure
- One application is the use of _______ fans
- off
- rise in head pressure, turning condenser fan on
- large variances
- multiple fans
Fan Speed Control for Controlling head pressure
- As the outside temperature _____, the fan slows down
- As the outside temperature rises, the fan speeds ___
- Some controls monitor the refrigerants condensing __________
- Newer generation systems use ____, to control condenser fan motor speed
- drops
- up
- temperatures
- VFD’s
Air volume Control for controlling head pressure:
- accomplished with a piston-driven ______ controlled with the ____-pressure refrigerant
- When there are multiple fans, the first fans can be cycled off using ________, and the shutter can be used on the _____ fan
- piston-driven damper controlled with high-pressure refrigerant
- using temperature, shutter can be used on the last fan
Condenser Flooding and Condenser Splitting for controlling head pressure:
- Condenser flooding devices cause liquid refrigerant to move from an oversized receiver to the condenser in ____ weather
- And requires a large amount of refrigerant to flood the _______ in the winter
- Splitting is another way to reduce the amount of extra ________ charge
- It splits the condenser into two separate _______ condenser circuits
- in cold weather
- condenser
- extra refrigerant charge
- two separate identical
Pressure Switches and Controls: Start and stop current flow to components;
- Low pressure switch: _____ on rise in pressure
- High pressure switch: ____ on rise in pressure
- Low ambient control: _____ on rise in pressure
- Oil safety switch: has a _____ delay; _____ on rise in pressure
- closes
- opens
- closes
- time delay, opens
Low pressure control applied as a thermostat:
- Can be set to operate the compressor the maintain the space temperature in the cooler and to serve as a ___-charge protection as well
- No interconnecting wires must be installed between the inside of the cooler and the _______ unit
- Control is rated by pressure range and ______ draw of the contacts
- low charge
- condensing unit
- current draw
High-pressure control:
- Prevents compressor from operating at high _____ pressures
- Opens on a ______ in pressure
- Can be automatically or manually ______
- Control cut-in point must be above the pressure corresponding to the _______ temperature
- Some have a fixed differential of ___psig
- Some manufacturers specify a manual ______
- head
- rise
- reset
- ambient
- 50psig
- reset
Oil Pressure Safety Control:
- Larger compressors use with _____ pumps
- Pump is connected to compressor _______ and oil is forced through ______ in crankshaft
- Measures ___ oil pressure
- oil pumps
- crankshaft, holes
- net
The Solenoid Valve:
- Valve position controlled by a solenoid ______
- Normally ____ or normally ______
- Used to control ______ or _______ flow
- Valves must be installed with arrow pointing in direction of ______
- coil
- open or closed
- liquid or vapour flow
- flow
Automatic Pumpdown systems: Sequence of pumpdown operation;
- Normally closed liquid-line solenoid valve controlled by a _________
- Thermostat opens when desired ____ temperature is reached
- The solenoid deenergizes and _______
- Comp continues to pump ref downstream of closed solenoid valve to the high side causing low side pressure to _____
- thermostat
- box temp
- closes
- drop
Automatic Pumpdown Systems: Call for Cooling:
- When box temp rises, thermostat ______
- Liquid line solenoid is _______
- Refrigerant flows to _______
- when low side pressure increases, the low pressure control _____
- the compressor is once again _______
- closes
- energized
- evaporator
- closes
- energized
Medium-Temp Refrigeration:
- Box temperature ranges from __F to 45F
- Coil temps are normally 10 to ___F cooler than the box
- Coil temp as low as ___F
- 34 to 45F
- 10 to 15F
- 19F
Random or Off-Cycle Defrost:
- Most _______ type of defrost
- Occurs when refrigeration system has enough reserve capacity to cool more than the _____ requirement
- Air in the cooler can defrost ice from the coil and evaporator fans continue to ___
- common
- load
- run