Piping Ppt Flashcards
Types of refrigeration and air conditioning tubing:
K - ______duty ( _____ wall)
L - ______ wall thickness
M - ______ duty (____ wall)
Type __ is most common in this trade
K - heavy duty (thicker wall)
L - Regular wall thickness
M - Light duty (thin wall)
Type L is most common
Goal of good refrigeration piping:
- Provide for economical refrigerant line sizing without excessive ________ drops
- Ensure adequate refrigerant _____ to _________
- Prevent unplanned _______ of oil in system piping
- Prevent the compressor from ______ of liquid refrigerant or oil
- excessive pressure drops
- flow to evaporator
- trapping of oil
- slugging
Guide lines to insure the above:
- Keep lay out ______
- Keep number of joints to a ________
- Keep lines as _____ as possible
- Avoid unnecessary _____
- Use _____ down system whenever possible
- Properly support _______
- Install proper _______ elimination devices when required
- simple
- minimum
- small
- traps
- pump down
- piping
- vibration
Refrigerant piping priorities:
- Most sensitive is the _______ line
- Less sensitive are the Condensate line, ___ gas line, and _____ line
- suction line
- condensate line, hot gas line, and liquid line
note: generally in that order
Pressure Drop in piping is controlled by the following: (4)
- pipe _______
- pipe ______
- number of _________
- fluid ________
- Pipe Diameter
- Pipe length
- number of fittings
- fluid velocity
Suction line design and installation:
Common goal limit suction line to __F equivalent pressure drop
2F
Suction line design and installation:
- Return ___ back to the compressor under all load conditions
- Prevent oil from draining from active and inactive _________
- Prevent liquid refrigerant from draining back to the _________ during the off cycle
- Prevent unnecessary _____ gains and the line sweating
- oil
- evaporator
- compressor
- heat gains
Suction line design and installation:
- Ensure minimum gas velocity ___fpm from horizontal runs
- Ensure minimum gas velocity of ____fpm from vertical risers (travelling up)
- Ensure max velocity of ____fpm is not exceeded
- Ensure trap is installed at the base of all suction line risers over __ft (good up to 25ft of rise)
- 500fpm
- 1000fpm
- 4000fpm
- 8ft
Suction line design and installation:
- Use double suction risers if system can reduce capacity down to ___% of full load
- Insure high compression ratios are _______
- Pitch horizontal runs 1/2” down every ___ft in direction of flow
- Use _____ at the top of coil when pump down control is not used
- 50%
- avoided
- 10ft
- loops
Suction line design and installation:
Ensure ___” of suction line within the conditioned space before exiting
18”
Hot gas line design and installation:
Common goals limit hot gas line to __F equivalent pressure drop
2F
Hot gas line design and installation: Goals:
- Ensure oil leaving the compressor travels to the _________
- Avoid _________
- Use proper ________ devices
- Prevent refrigerant migrating back to the compressor during ____ cycles
- condenser
- trapping
- vibration
- off cycles
Hot gas line design and installation:
- Ensure minimum gas velocity of ____fpm for horizontal runs
- Ensure minimum gas velocity of ______ fpm for verticals risers
- Trap at base of all hot gas risers over 8ft (good up to ___ft)
- 500
- 1000
- 25ft
If vertical velocity is less than 1000fpm then a double ______ should be installed
riser
Hot gas design and installation:
- Use double hot gas risers if system capacity drops to ___% of full load
- Ensure a max gas velocity of _____fpm is not exceeded
- pitch all horizontal runs 1/2” every 10ft in direction of _____
- 50%
- 4000fpm
- flow