Which of the following is a function of refrigerant loop components?
a) control refrigerant flow
b) maintain proper refrigerant quantity and quality in the system
c) both A and B
d) Neither A or B
c) both A and B
A measurable pressure drop between the evaporator outlet and compressor inlet may indicate that the ________ should be replaced
a) liquid line filter-drier
b) liquid receiver
c) sight glass
d) suction line filter-drier
d) suction line filter-drier
Large systems store liquid refrigerant on the high side in the _________
a) liquid line filter-drier
b) liquid receiver
c) sight glass
d) suction line filter-drier
b) liquid receiver
The best place to install a sight glass is _______
a) between the metering device and distributor
b) in the discharge line
c) just after the liquid line filter-drier
d) just after the suction line filter-drier
c) just after the liquid line filter-drier
A riser valve is a valve installed _______
a) in the compressor discharge line
b) in a length of vertical refrigerant line
c) on the condenser
d) in a liquid line manifold
b) in a length of vertical refrigerant line
Which of the following statements regarding service valves is not true?
a) service valves are fastened to tubing using soldered connections
b) service valves provide access for taking pressure readings
c) many systems have a service valve at the outlet of the liquid receiver
d) many service valve stems must be turned using a refrigeration service valve ranch
a) service valves are fastened to tubing using soldered connections
A check valve might be used _______
a) to allow refrigerant to bypass one of two metering devices in a heat pump system
b )in multiple-evaporator systems to prevent refrigerant from warmer evaporators from backing up into colder evaporators
c) to prevent unwanted refrigerant migration during the Off cycle of large commercial systems
d) all of the above
all of the above
In a multiple evaporator system, a check valve is installed at the _______
a) compressor inlet
b) condenser inlet
c) outlet of the warmest evaporator
d) outlet of the coldest evaporator
d) outlet of the coldest evaporator
A solenoid valve that opens a small valve that directs pressure to open and close a larger valve is ________
a) direct-acting
b) normally closed
c) pilot-operated
d) all of the above
c) pilot-operated
Ice accumulation on an evaporator can be quickly melted by automatically opening a system’s ________
a) hot gas defrost
b) liquid receiver
c) manifold valve
d) moisture indicator
a) hot gas defrost
A ________ valve alleviates low pressure and temperature conditions by diverting some refrigerant vapour from the compressor discharge directly to the low side
a) desuperheater
b) hot-gas bypass
c) relief
d) riser
b) hot-gas bypass
A hot-gas bypass valve directs hot-gas refrigerant from the discharge line to the ________
a) condenser
b) liquid line
c) liquid receiver
d) low side of the system
d) low side of the system
The purpose of a crankcase pressure regulator is to _________
a) ensure that compressor discharge pressure is sufficiently high
b) increase liquid line pressure in low-ambient conditions
c) maintain a sufficiently low pressure in the compressor
d) show the flow of liquid refrigerant
c) maintain a sufficiently low pressure in the compressor
A commercial refrigeration system with a single suction line and multiple evaporators can maintain a different temperature at each evaporator by controlling and differing
a) crankcase pressure
b) evaporator pressure
c) head pressure
d) liquid line temperature
b) evaporator pressure
The purpose of an evaporator pressure regulator is to ______
a) bypass liquid line refrigerant around the metering device
b) control evaporator temp by controlling its pressure
c) isolate parts of the system for service
d) shut off the compressor if evaporator pressure gets too high
b) control evaporator temperature by controlling its pressure