RACT Unit 22 Review questions/Practice test Flashcards
Why are some water-cooled condensers cleaned with brushes and others with chemicals?
a) chemicals are only used on outdoor condensers, indoor condensers are cleaned with brushes
b) some water-cooled condensers will accumulate scale while others do not
c) all water-cooled condensers are hermetically sealed and cannot be cleaned with brushes
d) some condenser tubes are not straight and will not allow brushes to pass through them
d) some condenser tubes are not straight and will not allow brushes to pass through them
The three materials of which air-cooled condensers are normally made are _______
a) brass, aluminum, and cast iron
b) brass, copper, and steel
c) copper , aluminum, and steel
d) copper, cast iron, and brass
C) copper, aluminum, and steel
One of the differences between air-cooled and water-cooled condensers is the _______________
A) compressor discharge line temperature
B) Type of compressor used
C) Refrigerant condensing temp
D) Type of refrigerant used
Refrigerant condensing temperature
When is the most heat removed from the refrigerant in the condensing process?
A) when the liquid refrigerant leaves the condenser
B) when the vapour enters the receiver
C) During the change in state from a liquid to a vapour
D) During the change in state from a vapour to a liquid
D) during the change in state from a vapour to a liquid
After heat is absorbed into the water in a water-cooled condenser, the water can be ____________
a) treated with chemicals and piped to a chiller
b) wasted down the drain or sent to a cooling tower
c) filtered and used for drinking water
d) filtered and then treated with chemicals before being reused domestically
b) wasted down the drain or sent to a cooling tower
A water-cooling tower capacity is governed by what aspect of the ambient air temp?
a) dry-bulb temperature
b) wet-bulb temperature
c) altitude
d) enthalpy of the air
b) wet-bulb temperature
When a standard-efficiency air-cooled condenser is used, the condensing refrigerant will normally be _________ above the ambient air temperature
A) 15F
B) 60F
C) 45F
D) 30F
30F
Fan cycling, air shutters or dampers, condenser flooding, and VFD condenser fan motors are all methods for controlling __________
a) evaporator capacity
b) electrical efficiency
c) suction pressure
d) head pressure
d) head pressure
An outdoor air-cooled condenser that has a vertical coil can be affected by the ___________
A) refrigerant oil type
B) prevailing winds
C) indoor ambient temperature
D) municipal water temperature
B) Prevailing winds
Air-cooled condensers are ______________
a) being phased out due to their inefficiencies
b) much more efficient than water-cooled cond.
c) less efficient than water-cooled condensers
d) the most efficient condensers on the market
c) less efficient than water-cooled condensers
The type of condenser that has straight copper tubes that are fastened into an end sheet within a steel shell that is typically used in large installations is the _____________ condenser
a) shell-and-tube
b) shell-and-coil
c) tube-within-a-tube
d) air-cooled
a) shell-and-tube
On a system that uses a floating head pressure, ____________________
a) the condenser must be located outdoors
b) more system heat is available for heat reclaim coils
c) the amount of heat discharged from the condenser is extremely high
d) less system heat is available for heat reclaim coils
d) less system heat is available for heat reclaim coils
When the hot discharge gas enters the compressor, it is first _______________
a) condensed
b) de-superheated
c) vaporized
d) sub-cooled
De-superheated
A 2-ton wastewater system that operates approximately 16hours per day would use about __________gallons of water per day
a) 5760
b) 2880
c) 7880
d) 11,520
2880?
A 10-ton water-cooled system that recirculates water through a cooling tower averages 16 hours of run time per day. The amount of water that would be circulated in a day would be about __________ gallons
3 x 10 x 16 x 60 = 28,800