Quiz Questions that were wrong Flashcards

1
Q

Gas/Steam Controls
What safety device protects steam boiler from high pressure?
What is the setting on that device?

A

A Relief Valve.
15 psi.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Gas/Steam Controls
What device detects a blocked flue passageway inside a boiler?

A

Flame Roll Out
(F.R.O.)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Gas/Steam Controls
What detects a blocked flue pipe or chimney way?

A

Spill Switch
(S.S.)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Gas/Steam Controls
Terminals 1-2 on a low water cut off are used in the ________ circuit

A

The Burner/Safety Circuit

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Gas/Steam Controls
Terminals 3-4 are used for what on a low water cut off?

A

Automatic Feeder

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Gas/Steam Controls
The main steam vent should be installed ________ inches from the end of a steam main.

A

15

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Gas/Steam Controls
What control can be installed on a steam boiler to add water?

A

Automatic Feeder

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Aquastats
Using a high-limit and low-limit aquastat, will the circulator run if the low limit is not satisfied and there is a call for heat?

A

No.
(It would be pointless to circulate cold water)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Aquastats
Low-limit is most commonly used on a boiler with a:
a. indirect heater
b. flat plate heat exchanger
c. water heater
d. tankless coil

A

d. tankless coil

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Aquastats
Terminals C1 and C2 put out ________ volts

A

120 volts A.C.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Aquastats BONUS-5 points
When do you need a 2nd hi-limit control and why? (must have both correct)

A

WHEN: there are 3 or more zones and an indirect heater.
WHY: in case the first hi-limit control fails.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Zone Controls
If you have 4 zones and are zoning with zone valves, how many circuators are needed?
a. 4
b. 2
c. 1
d. none

A

c. 1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Zone Controls
What is the maximum number of zone valves that you can install on a 40 va transformer?
a. 1
b. 3
c. 40
d. none

A

b. 3

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Zone Controls
When the end switch is made on a zone valve, what voltage comes from the end switch?
a. 24 volts
b. 120 volts
c. 240 volts
d. none

A

d. none

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Zone Controls
When using a relay pack how many transformers are needed in the relay pack?
a. 1
b. 2
c. as many as there are zones
d. none

A

a. 1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Zone Controls
When using zone valves you must wire them with what voltage to the motor?
a. 240 volts
b. 120 volts
c. none
d. 24 volts

A

d. 24 volts

17
Q

Zone Controls BONUS-5 POINTS - MUST HAVE BOTH CORRECT
Can you zone steam? If so what type of zone valve has to be used? Explain in detail for full credit.

A

Yes. Must use a slow opening (3-5 minutes) zone valve.