Power Venters Flashcards
Power Venters must be installed At Least _______ Foot Above Doors or Windows.
Power Venters must be installed At Least 1 Foot Above Doors or Windows.
Power Venters must be installed At Least _______ Feet Above Public Walkways.
Power Venters must be installed At Least 7 Feet Above Public Walkways.
Power Venters must be installed At Least _______ Feet To The Side Of Any Doors Or Windows.
Power Venters must be installed At Least 4 Feet To The Side Of Any Doors Or Windows.
Power Venters must be installed At Least _______ Foot Above Finished Grade.
Power Venters must be installed At Least 1 Foot Above Finished Grade.
Power Venters must be installed At Least _______ Feet Above Any Outside Air Intake Within _______ Feet.
Power Venters must be installed At Least 3 Feet Above Any Outside Air Intake Within 10 Feet.
Power Venters must be installed At Least _______ Feet Below Windows.
Power Venters must be installed At Least 4 Feet Below Windows.
Power Venters must be mounted At Least _______ Feet From The Inside Corners Of A Building.
Power Venters must be mounted At Least 3 Feet From The Inside Corners Of A Building.
Sequence of Operation for a power vent:
1.
2.
3.
Sequence of Operation for a power vent:
1. Call for heat
2. Power venter turns on
3. Pressure switch on power venter makes contact close and sends power to burner.
When is a draft inducer used?
when a natural draft chimney does not produce good draft.
A and B terminals are used as a/an ______ switch.
an end switch
What does a power vent do?
exhausts the products of combustion by means of mechanical draft.
Power venters can be used for what kind of fuel?
natural gas, L.P. gas, and fuel oil.
2 manufacturers of power venters are _________ and _________.
Fields and Tjernlund.
Field Terminals:
L1:
L2:
T1:
T2:
T3:
B1:
B2:
Field Terminals:
L1: Hot 120 volts
L2: Neutral 120 volts
T1: Hot 24 volts from R on Transformer or B1 on Aquastat
T2: Neutral from TH of Transformer or gas valve or B2 on Aquastat
T3: TR on gas valve
B1: T1 (24 volts AC)
B2: T2 TH on gas valve (24 volts AC)