Quiz 5 - Commercial Wiring - Unit 8 Flashcards
All panelboards are to be CSA approved.
True
False
According to 12-3024 all unused openings shall be,
Closed by covering with tape
Closed by plugs or plates
Closed by devices and/or plates
All of the above
Typical panelboard arrangement has,
OCD adjacent connections on the same phase
OCD adjacent on separate phases
OCD across from each other on the opposite phase
OCD across from each other on same phase
All of the above
Both A and C
Both B and D
Both A and D
A circuit directory,
Is not necessary in some cases
Is necessary with only residential installations
Is necessary only with commercial installations
Is normally located on the face or inside the panel door
The ungrounded conductor can be green or any other colour.
True
False
4-032(3c) requires the neutral to be white and,
A,B,C phases are Black, Blue, Red respectively
A,B,C phases are Black, Red, Blue respectively
A,B,C phases are Red, Black, Blue respectively
Both A and C
According to 14-606(1) and Figure 8-6
A panelboard OCD shall be rated the same as the feeder overcurrent device
A panelboard OCD shall be rated greater than the rated busbar
A panelboard OCD shall be rated, at maximum, equal to the rated busbar
Both A and C
For figures 8-9, 8-10, and 8-11, the tip to tail method for vector addition can be used for solving the neutral current.
True
False
4-018 allows sets regulation for neutral sizing and
Assumes all connected loads are resistive
Assumes there are no unbalanced loads
Assumes the unbalanced load is equal across all phases
All of the above