Quiz 3 - Commercial Wiring - Unit 2 Flashcards
Figure 2-3 is indicating
26-240(2) - the enclosure must be locked
12-012 - rules for underground conductors in conduit
6-300(3) - an underground entrance to a building must be sealed
All of the above
Figure 2-4 is indicating,
A busway (bus duct) is connecting the utility transformer to the main switch
A busway (bus duct) is connecting the utility transformer to the secondary switches
A busway (bus duct) is connected underground
Transformers use liquids (oil/synthetic) to reduce heat at the core of the transformer.
True
False
Oils containing PCB’s require a safe steps for disposal.
True
False
Dry-type transformers are cooled by open air flow and/or fans.
True
False
Figure 2-6 is indicating a basic transformer connection between the high voltage primary and the distribution.
True
False
Figure 2-9 is indicating,
A system that is grounded at the first point of distribution (secondary)
A 3 phase primary 600V to secondary 208/120V transformer connection
Primary feed is Delta configured and the Secondary is Wye configured
All of the above
Figure 2-11 is indicating
A neutral is achieved by grounding the coil of a transformer
The neutral is grounded on the secondary
The neutral is grounded on the primary
Both A and B
Figure 2-12 is indicating
The primary side is expressed as H1, H2
The secondary side is expressed as X1, X2
The primary and secondary are both Delta configurations
All of the above
The most commonly used system for modern commercial buildings is the 3 phase, 4-wire wye system.
True
False
Figure 2-14 is indicating,
Potential and Current transformers are connected around the high-voltage section of a substation
Watt-hour and Varhour meters are monitoring a delta configured autotransformer
The high voltage line feed is 4160V
All of the above
Figure 2-16 is indicating,
A 1,200A 3 phase main
All sections of the switchboard must be bonded together
Bonding must be in accordance with 10-616
A #6 AWG is connected to the water main
Three 4” conduits containing 750MCM conductors are feeding the service
All of the above
Table 2-3 is showing an underground configuration for conductors in raceways according to T-D11.
True
False
Figure 2-16 and 2-17 are two images of the same service equipment.
True
False
Grounding isn’t used for saving lives and protecting equipment.
True
False