Primary Reformer Trips Flashcards
Primary Reformer Fuel Gas trips
Low= .9psig
High= 26psig
Flue Gas Temperature trip (ID Fan protection)
670 degrees F
Flue Gas Temperature trip to Low Fire (Temp Coil protection)
618 degrees Fahrenheit for 30 seconds
Process Steam Trip
47.5 MLBs./hour
Process Feed Gas Trip
250 MSCF/Hour
Secondary Reformer Transfer Header jacket water level
10 minute timer
Primary Reformer Transfer Header jacket water level
10 minute timer
Secondary Process Condensate K.O. Drum
Primary Reformer Radiant Outlet Temp Trips
1650 degrees Fahrenheit
Primary Reformer Common Header Temp Trip
1600 degrees Fahrenheit
Primary Reformer Common Header Temp Trip to Minimum Fire
1575 degrees Fahrenheit
All ID Fans Total Flow (inferred)
3000 MSCF/ Hour
Primary Reformer CO trip
200 PPM
All ID fans total flow (inferred) minimum fire
2000 MSCF/ Hour
Primary Reformer CO Minimum Fire
200 PPM