Born Purge Gas Skid Downstream Pressure high trip
27 psig
Born Purge Gas Skid Upstream Pressure low trip
1.6 psig
Born Purge gas Burner low pressure trip
1.6 psig
Born Fuel gas downstream pressure High trip
23.25 psig
Born fuel gas downstream pressure low trip
1.6 psig
Born fuel gas burner pressure low trip
1.6 psig
Born Inferred low air flow
1050 MSCF/ Hour and greater than 100 PPM of CO
Born Inferred low air flow minimum fire
1200 MSCF/ Hour and greater than 100 PPM CO
Born High Firebox pressure trip
0 InWC on PT-2115A
0 InWC on PT-2115AA
.1 InWC on PT-2115C
Born Convection Section outlet temp trip
575 degrees Fahrenheit
Steam Drum water level trip
0%
Trips the Born
Steam Drum Boiler Circulation Flow trip
2200 GPM
Trips the Born
Born Instrument Air supply Low trip
40 psi
Born Instrument Air supply High trip
100 psig
Born Pilot gas downstream pressure High trip
20 psig