Practice Test 2 Flashcards

Prepare for the IPC exam with practice tests and review questions.

1
Q

What is the required pipe size for a vertical stack with the discharge from 5 branch intervals carrying 200 drainage fixture units?

A

8”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Calculate the measurement for a special case 90 degree offset using 45 degree elbows for M if the spread between pipes is 14”.

See Practice Problem Figure 8-7

A

10 5/8”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Fill in the blank:

In non bearing partition walls, a stud shall not be notched in excess of ______ percent of its depth.

A

40

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What size of storm drain pipe should be installed for a vertical roof drain that has a gallon per minute flow of 450 gpm?

A

6”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the minimum slope for a horizontal pipe that is 8 inches in diameter?

A

1/16” per foot

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Fill in the blank:

Every dry vent shall connect to a horizontal drain pipe ______ the center line.

A

above

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Which of the following devices is NOT to be installed for high hazard backflow situations?

a. reduced pressure principle backflow prevention assembly
b. air gap
c. backflow preventer with intermediate atmospheric vents
d. hose connection vacuum breaker

A

c. backflow preventer with intermediate atmospheric vents

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the grease retention capacity for an interceptor with a flow through rate of 20 gpm?

A

40 pounds

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Convert:

37.4 gallons to cubic feet

A

5 cubic feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What are the total drainage fixture units at point C?

Examine Figure 8-8

A

32 DFU

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Fill in the blank:

Shut off valves for gas appliances located at a manifold shall be within ______ feet of the appliance served.

A

50

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is the required air pressure for an air test on drainage and vent pipe systems?

A

5 psi

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What is not a listed color for CPVC glue?

A

purple

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Fill in the blank:

When work is performed ______ feet above lower levels, fall protection is required.

A

6 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is the minimum trap size for a drinking fountain?

A

1 1/4”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What is the pipe size given the following information:

Schedule 40 Metallic Pipe
Natural Gas 2.0 psi
Pressure Drop 1.0 psi
Developed Length 150 feet
Cubic Feet Per Hour 2000

A

1 1/4”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

What is the maximum travel distance to a drinking fountain in a typical public area, not including a covered mall?

A

500 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

Which of the following devices is for use on backsiphonage situations only?

a. air gap
b. reduced pressure principle backflow preventer assembly
c. laboratory faucet backflow preventer
d. anti siphon-type fill valves for gravity water closet flush tanks

A

d. anti siphon-type fill valves for gravity water closet flush tanks

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

Find the grade of a pipe if the drop is 21” and the run is 84 feet.

A

1/4” per foot

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

The potable water supply shall be protected at the connection of a fire sprinkler system by
use of which device?

A

double check backflow prevention assembly

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

What is the minimum horizontal hanger spacing for 2” copper tubing?

A

10 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

What is the required pipe size for a vertical stack with the discharge from three branch intervals carrying 600 drainage fixture units?

A

6”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

Find the drop if the percentage grade is 2% and the run is 65 feet.

A

16 1/4”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

What is the required pipe size for a horizontal branch drain carrying 140 drainage fixture units?

A

4”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
Q

What is the drainage fixture unit value for a shower receiving 6.5 GPM?

A

3

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
26
Q

What is the minimum size cleanout for a 6” pipe?

A

4”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
27
Q

Fill in the blank:

The effluent level in a sewage ejector sump shall be maintained at all times to prevent effluent in the sump from rising within ______ inches of the invert gravity drain inlet into the sump.

A

2”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
28
Q

What is the minimum width for a passageway of a room containing appliances in a building that is not for dwelling units?

A

36”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
29
Q

The horizontal distance from the fixture outlet to the trap weir shall not exceed ______ inches.

A

30”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
30
Q

Fill in the blank:

What is the minimum width for a toilet compartment partition?

A

30”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
31
Q

What is the vent pipe size for a drainage system serving a 4” stack carrying 400 DFU with a developed length of 165 feet?

A

4”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
32
Q

Fill in the blank:

Oil separators shall have a depth of not less than ______ feet below the invert of the discharge drain.

A

2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
33
Q

What are the total drainage fixture units at point A?

Examine Figure 8-9

A

24 DFU

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
34
Q

Fill in the blank:

A cleanout at the junction of the building drain is required at the junction or within ______ feet upstream from the junction.

A

10

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
35
Q

Fill in the blank:

The person acting as code official is ______.

A

appointed by local authority

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
36
Q

What is the maximum slope for a pipe that is used in a combination waste and vent system?

A

1/2” per foot

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
37
Q

Convert:

12.46’ to feet and fractional inches

A

12’ 5 1/2”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
38
Q

Fill in the blank:

The duration of a test on a gas piping system shall not be required to exceed ______ hours.

A

24

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
39
Q

What is the maximum DFU for a common vent serving a 2” drain?

A

4

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
40
Q

What is the minimum drain size for an emergency eye wash station?

A

no drain required

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
41
Q

Fill in the blank:

Wall materials for a bathtub or shower shall extend to a height of not less than ______ inches above the drain of the tub or shower.

A

70

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
42
Q

Calculate the diagonal for a rolling offset made with two 45 degree fittings which has a rise of 12 inches and an offset of 14 inches.

A

26.07 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
43
Q

Find the area of a square that is 33’ 6” on each side.

A

1122 square feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
44
Q

Fill in the blank:

A combination plumbing fixture is permitted to be installed on one trap provided that the waste outlets are not more than ______ inches apart.

A

30

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
45
Q

Solve for the gallon per minute for a roof surface that is 4,000 square feet at a location with 1 inches of rainfall intensity per hour.

A

42

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
46
Q

What is the vent diameter of a double-wall gas vent given the following information:

Single Appliance.
Category 1 Connected directly to appliance vent
Vent Height 20’
Lateral Length 5’
Appliance BTU = 140,000 Natural Draft

A

5”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
47
Q

Convert:

7.75” to fractional inches

A

7 3/4”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
48
Q

Convert:

5.625’ to feet and fractional inches

A

5’ 7 ½”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
49
Q

Fill in the blank:

A tracer wire with a size of not less than ______ AWG shall be installed for non metallic water service pipes for Group I-2, Condition 2 facilities.

50
Q

What is the vent pipe size for a drainage system serving a 6” stack carrying 1800 DFU with a developed length of 150 feet?

51
Q

Fill in the blank:

Shoring in a trench excavation must extend down to within ______ inches of the bottom of the trench.

52
Q

Find the area of a tank that has a diameter of 48 inches.

(Use Pi = 3.14)

A

1808 square inches

53
Q

True or False:

The discharge pipe serving a temperature and pressure relief valve shall not have any tee fittings.

54
Q

Convert:

25’ 10 7/8” to decimal feet

55
Q

Fill in the blank:

A wire basket on the discharge side of a clothes washer shall prevent passage of solids ______ inch(es) or larger from being discharged into the public sewer.

56
Q

Fill in the blank:

Stack-type air admittance valves shall be located not less than ______ inches above the flood level rim of the fixture drain being vented.

57
Q

Fill in the blank:

Extension ladders are to extend ______ above the upper landing surface.

58
Q

Convert:

77,760 cubic inches into cubic feet

A

45 cubic feet

59
Q

Fill in the blank:

Cleanouts for 8 inch pipe shall be provided with a clearance of not less than ______ inches.

60
Q

What is the maximum distance for a horizontal branch serving a water closet in a single stack vent system?

61
Q

Find the drop if the grade is 1/8” per foot and the run is 150 feet.

62
Q

True or False:

Waste receptors for indirect waste shall be permitted in concealed spaces such as crawl spaces, attics or plenums.

63
Q

What size is the horizontal gutter if the slope is ¼” per foot and the flow rate is 157 gpm?

A

3” x 5”

64
Q

True or False:

Cleanouts are required on storm drainage with the same requirements as that of sanitary drainage systems.

65
Q

How much larger should a sleeve be in comparison to the pipe passing through it?

A

2 pipe sizes larger

66
Q

What is the maximum distance for a trap arm for a 2” trap with ¼” per foot grade?

67
Q

What is the drain pipe diameter for a water supply tank with a tank capacity of 1,100 gallons?

68
Q

Fill in the blank:

When backfilling a trench, loose earth shall be placed in the trench in ______ inch layers and tamped in place until the crown of the pipe is covered by 12 inches of tamped earth.

69
Q

What is the minimum diameter for a storm or ground water sump pit?

70
Q

What is the drainage fixture unit value for a bidet?

71
Q

Fill in the blank:

The fixture supply pipe shall terminate not more than ______ inches from the point of connection to the fixture.

72
Q

Fill in the blank:

The maximum horizontal length of a Type B double-wall gas vent connector shall be ______ percent of the height of the vent.

73
Q

What is the minimum flow rate in gallons per minute for a shower?

74
Q

Which color is used to indicate a non potable water system?

75
Q

What is the smallest building drain or building sewer size that can be replaced by relining methods?

76
Q

How far above the roof shall a vent pipe terminate if a photovoltaic panel is mounted over the top of the vent opening?

77
Q

What is the minimum vent pipe size for terminations that are located in areas where 97.5 percent value for outdoor design is 0 degrees Fahrenheit?

78
Q

Fill in the blank:

Gas appliance venting systems shall be designed and constructed so as to convey all flue and vent gasses ______.

A

to the outdoors

79
Q

What is the maximum total developed length for a pipe running from a fixture to an indirect waste location?

80
Q

Fill in the blank:

Manholes for drainage pipes in a building shall be located not more than ______ feet apart.

81
Q

True or False:

A code official can be held personally liable for damages caused that result from enforcement of the code.

82
Q

What is the minimum number of drinking fountains required in a bank?

A

1 per 1000 persons

83
Q

What is the vent size at point D in Figure 8-10 if the developed length of the vent is 75 feet?

Examine Figure 8-10

84
Q

What is the maximum DFU for a waste stack vent serving a 3” drain?

85
Q

Fill in the blank:

Horizontal branches at the base of stacks shall connect at a point not less than ______ times the diameter of the drainage stack downstream from the stack.

86
Q

Fill in the blank:

If the building sewer is not constructed of materials listed in Table 702.2, the water service pipe shall be horizontally separated by not less than ______ feet of undisturbed earth.

87
Q

Fill in the blank:

Standpipes intended for indirect waste shall not extend less than ______ inches above the trap weir.

88
Q

Convert:

6 7/16” to decimal inches

89
Q

Fill in the blank:

Through-the-wall vent terminal shall terminate not less than ______ feet from an inside corner of the building.

A

no clearance required

90
Q

What is the maximum cubic feet per hour given the following information:

Schedule 40 Metallic Pipe
Natural Gas Less than 2 psi
0.5 inch w.c.
Developed Length 60 feet
Pipe Size 1”

91
Q

What is the minimum slope required for condensate drain piping from a fuel-burning appliance?

92
Q

Fill in the blank:

The vent system serving a building drain shall have not less than ______ vent pipe that extends to the outdoors.

93
Q

What pipe size is required for a building drain carrying 1100 DFU if the pipe has 1/8” per foot slope?

94
Q

Fill in the blank:

The discharge from commercial dishwashers shall discharge through an indirect waste connection by means of ______.

A

either air gap or air break

95
Q

What is the minimum fixture water supply pipe size for a toilet with a flush tank?

96
Q

Find the drop if the grade is ¼” per foot and the run is 80 feet.

97
Q

What is the minimum dimension of air openings for outside combustion air?

98
Q

Fill in the blank:

Combustion air communicating with the outdoors through one permanent opening shall have an opening of 1 square inches for every ______ Btu/h rating of the total of all appliances served.

99
Q

What is the minimum drain size for an automatic clothes washer?

100
Q

Calculate the diagonal for a pipe that offsets 10 inches using two 45 degree fittings.

A

14.1 inches

101
Q

A toilet costs $645.00 at the supplier. The plumber will sell the faucet with a markup of 35%. What is the new price for the faucet?

102
Q

Convert:

200 gallons into weight measurement in pounds

A

1666 pounds

103
Q

What is the minimum size for any sanitary drainage vent?

104
Q

Calculate the measurement for M if the spread between pipes is 17” and J is 18”.

See Final Test Figure 8-11

A

10 15/16”

105
Q

Fill in the blank:

Each fixture trap shall have a trap seal of not more than ______ inches deep.

106
Q

Fill in the blank:

Water service pipe installed underground outside the structure shall have a pressure rating of not less than ______ psi at 73.4 degrees F.

107
Q

How tall is a water tower if the pressure at the base is 75 psi?

108
Q

What is the minimum size wire for a bonding jumper for CSST?

A

6 AWG copper

109
Q

Fill in the blank:

Strainer plates on drain inlets are not to have openings any larger than ______ inch in least dimension.

110
Q

Fill in the blank:

Secondary roof drain systems shall have an end point of discharge ______ the primary system.

A

separate from

111
Q

What is the minimum fixture water supply pipe size for a lavatory?

112
Q

What is the minimum flow pressure in psi for a public lavatory?

113
Q

True or False:

A clothes dryer is permitted to be installed in a bathroom.

114
Q

What size of storm drain pipe should be installed for a horizontal roof drain that has a slope of ½” per foot and a gallon per minute flow of 100 gpm?

115
Q

What pipe size is required for a building drain carrying 150 DFU if the pipe has 1/8” per foot slope?

116
Q

What is the maximum spacing for piping supports when installing 1” steel gas pipe?

117
Q

Fill in the blank:

The size of storm drain piping shall be based on ______.

A

gallons per minute flow through the roof drain

118
Q

Fill in the blank:

When installed in an attic, water heaters shall be provided with a level working space not less than ______ inches in length and width.

119
Q

What are the total drainage fixture units at point B?

Examine Figure 8-12

120
Q

What is the minimum vertical hanger spacing for 1” PEX tubing?