Plumbing 4th Importance Flashcards
The__________________is required to maintain
sanitary and safe operation conditions in plumbing and drainage systems that are under the jurisdiction of the Authority Having Jurisdiction.
The owner or the owner’s designated agent shall be responsible for maintenance of plumbing systems. To determine compliance with this subsection, the Authority Having Jurisdiction shall be permitted to cause a plumbing system to be reinspected.
Ice makers and storage chests must be located in supervised areas such as nurses stations to prevent:
Contamination
Ice makers or ice storage containers shall be located in nursing stations or similarly supervised areas to minimize potential contamination.
A bed pan steamer’s indirect waste pipe must have a trap seal of at least:
3 inches
A trap having a seal of not less than 3 inches (76 mm) shall be provided in the indirect waste pipe for a bedpan steamer.
An appendix referenced in this code shall not apply unless the appendix is specifically:
Adopted
The provisions in the appendices are intended to supplement the requirements of this code and shall not be considered part of this code unless formally adopted as such.
True or False: There is a preference in the code between gravity grease interceptors, hydromechanical interceptors, and engineered systems.
FalseA combination of hydromechanical, gravity grease interceptors, and engineered systems shall be allowed in order to meet this code and other applicable requirements of the Authority Having Jurisdiction where space or existing physical constraints of existing buildings necessitate such installations. A grease interceptor shall not be required for individual dwelling units or for private living quarters. Water closets, urinals, and other plumbing fixtures conveying human waste shall not drain into or through the grease interceptor.
Brazing alloys for nonferrous pipe for fuel gas may not be more than_____________phosphorus.
0.05 percent
Pipe joints shall be threaded, flanged, brazed, welded, or press-connect fittings that comply with CSA LC-4. Where nonferrous pipe is brazed, the brazing materials shall have a melting point in excess of 1000°F (538°C). Brazing alloys shall not contain more than 0.05 percent phosphorus. [NFPA 54:5.6.8.1]
(NFPA 54: National Fuel Gas Code)
Field wrapping shall provide equivalent protection and is restricted to those fittings and short sections where the factory wrap has necessarily:
Stripped
(1) Ferrous piping shall have a protective coating of an approved type, machine applied and in accordance with recognized standards. Field wrapping shall provide equivalent protection and shall be restricted to those short sections and fittings necessarily stripped for threading. Zinc coating (galvanizing)shall not be deemed adequate protection for piping or fittings. Approved nonferrous piping shall not be required to be wrapped.
Drinking fountains shall_________ be installed in public toilet rooms.
Not
Drinking fountains shall not be installed in toilet rooms.
_____________is the force exerted by a homogeneous liquid or gas, per unit of area, on the wall of the container.
Pressure
The normal force exerted by a homogenous liquid or gas, per unit of area, on the wall of the container. Residual Pressure. The pressure available at the fixture or water outlet after allowance is made for pressure drop due to friction loss, head, meter, and other losses in the system during maximum demand periods. Static Pressure. The pressure existing without any flow.
Where sleeves are used the outside annular space between the sleeve and the fire-resistance-rated assembly:
Shall be firestopped in accordance with this chapter.
Where sleeves are used, the sleeves shall be securely fastened to the fire-resistance-rated assembly. The (inside) annular space between the sleeve and the penetrating item and the (outside) annular space between the sleeve and the fire-resistance-rated assembly shall be firestopped in accordance with this chapter.
Systems must have an F rating of not less than
but no less than________________the required
fire resistance rating of the assembly being penetrated.
1 hour
Systems shall have an F rating of not less than 1 hour but not less than the required fire resistance rating of the assembly being penetrated.
All piping, fixtures, appliances, and appurtenances shall be___________supported in accordance with this Code.
Adequately
Piping, fixtures, appliances, and appurtenances shall be supported in accordance with this code, the manufacturer’s installation instructions, and in accordance with the Authority Having Jurisdiction.
A Type B-W gas vent shall terminate at least ____________feet in vertical height above the
bottom of the wall furnace.
12 feet
A Type B-W gas vent shall terminate at least 12 feet (3658 mm) in vertical height above the bottom of the wall furnace. [NFPA
54:12.7.2(3)]
(NFPA 54: National Fuel Gas Code)
A trap arm may change direction without the use of a cleanout when such change of direction does not exceed___________degrees.
90 degrees
A trap arm shall be permitted to change direction without the use of a cleanout where such change of direction does not exceed 90 degrees (1.57 rad). Horizontal changes in direction of trap arms shall be in accordance with Section 706.3. Exception: For trap arms, 3 inches (80 mm) in diameter and larger, the change of direction shall not exceed 135 degrees (2.36 rad) without the use of a cleanout.
Water Closet and Urinal Tanks shall be equipped with a listed__________.
Ballcock
Water closet and urinal tanks shall be equipped with a ballcock. The ballcock shall be installed with the critical level not less than1 inch (25.4 mm) above the full opening of the overflow pipe. In cases where the ballcock has no hush tube, the bottom of the water supply inlet shall be installed 1 inch (25.4 mm) above the full opening of the overflow pipe.
All showers shall be equipped with approved
_____________having an approved waterway.
Strainers
Showers shall have a waste outlet and fixture tailpiece not less than 2 inches (50 mm) in diameter. Fixture tailpieces shall be constructed from the materials specified in Section 701.2 for drainage piping. Strainers serving shower drains shall have a waterway at least equivalent to the area of the tailpiece.
(2018 UPC - 701.2 Drainage Piping.)
For rainwater supplied to drip irrigation systems, trap primers, urinals, and water closets, a filter allowing particulates up to _____________microns must be provided.
100
A filter permitting the passage of particulates not larger than 100microns (100 um) shall be provided for rainwater supplied to water closets, urinals, trap primers, and drip irrigation system.
Where the occupant creates surface water drainage, the sumps, gratings or floor drains shall be piped to a storm drain or an approved water__________.
Course
Where the occupant creates surface water drainage, the sumps, gratings, or floor drains shall be piped to a storm drainage or an approved water course.