Plumbing 3rd Importance Flashcards
Continuous wastes and fixture tailpieces for lavatories and similar fixtures shall not be less than____________inches O.D.
1-1/4 inches
Lavatories shall have a waste outlet and fixture tailpiece not less than 1-1/4 inches (32 mm) in diameter. Continuous wastes and fixture tailpieces shall be constructed from the materials specified in Section 701.4. Waste outlets shall be provided with an approved topper or strainer.
(2018 UPC - 701.4 Continuous Wastes.)
Metered faucets shall deliver not more than____________gallons of water per use.
0.25 gallons
Metered faucets shall deliver a maximum of 0.25 gallons (1.0 L)per metering cycle.
Sand and similar interceptors must have a minimum water seal of:
6 inches
Sand and similar interceptors for every solid shall be so designated and located as to be readily accessible for cleaning, shall have a water seal of not less than 6 inches (152 mm), and shall be vented.
The waste line in an oil and flammable interceptor must be a minimum of_____________
in diameter with a full-size cleanout to grade.
3 inches
The waste line shall be not less than 3 inches (80 mm) in diameter with a full-size cleanout to grade. Where an interceptor is provided with an overflow, it shall be provided with an overflow line [not less than 2 inches (50 mm) in diameter] to an approved waste oil tank having a minimum capacity of 550 gallons (2082 L) and meeting the requirements of the Authority Having Jurisdiction.
Each fixture trap shall have a water seal of not more than_____________inches.
4 inches
Each fixture trap shall have a liquid seal of not less than 2 inches(51 mm) and not more than 4 inches (102 mm), except where a deeper seal is found necessary by the Authority Having Jurisdiction. Traps shall be set true with respect to their liquid seals and, where necessary, they shall be protected from freezing.
If a plumbing system is lawfully in existence at the time of the adoption of this code, it is permitted to have its maintenance, repair or use continued, as long as no hazard to_____________
is created by such system.
Life, health, or property
Plumbing systems lawfully in existence at the time of the adoption of this code shall be permitted to have their use, maintenance, or repair continued where the use, maintenance, or repair is in accordance with the original design and location and no hazard to life, health, or property has been created by such plumbing system.
What may a reclaimed water system NOT be connected to?
Potable water system
Reclaimed (recycled) water systems shall have no connection to a potable water supply or alternate water source system. Potable water is permitted to be used as makeup water for a reclaimed(recycled) water storage tank provided the water supply inlet is protected by an air gap or reduced-pressure principle backflow preventer in accordance with this code.
What is the minimum clearance in front of water heater service panels mounted in an enclosure on the roof?
30 inches
Appliances on roofs shall be designed or enclosed so as to withstand climatic conditions in the area in which they are installed. Where enclosures are provided, each enclosure shall permit easy entry and movement, shall be of reasonable height, and shall have not less than a 30 inch (762 mm) clearance between the entire service access panel(s) of the appliance and the wall of the enclosure. [NFPA 54:9.4.1.1]
(NFPA 54: National Fuel Gas Code)
In cold climate areas, backflow assemblies and devices shall be protected from_______________by a method acceptable to the Authority Having Jurisdiction.
Freezing
In cold climate areas, backflow assemblies and devices shall be protected from freezing with an outdoor enclosure that complies with ASSE 1060 or by a method acceptable to the Authority Having Jurisdiction.
Forced draft systems shall be designed and constructed so as to develop a______________flow adequate to remove flue or vent gases to the outside atmosphere.
Positive
Forced draft systems and portions of induced draft systems under positive pressure during operation shall be designed and installed so as to prevent leakage of the flue or vent gases into a building.
[NFPA 54:12.4.3.3]
(NFPA 54: National Fuel Gas Code)
What is defined as an assembly of listed semirigid or flexible tubing and fittings to carry fuel between a fuel piping outlet and a fuel-burning appliance?
Appliance Fuel Connector
An assembly of listed semi-rigid or flexible tubing and fittings to carry fuel between a fuel piping outlet and a fuel-burning appliance
Rainwater tank openings must be protected to prevent the entrance of_________________into the tank.
All the above
Rainwater tank openings shall be protected to prevent the entrance of insects, birds and rodents into the tank. Rainwater tank access openings exceeding 12 inches (305 mm) in diameter shall be secured to prevent tampering and unintended entry by either a lockable device or other approved method.
Rainwater tank access openings exceeding
__________in diameter must be secured to prevent tampering and unintended entry by either a lockable device or other approved method.
12 inches
Rainwater tank openings shall be protected to prevent the entrance of insects, birds and rodents into the tank. Rainwater tank access openings exceeding 12 inches (305 mm)in diameter shall be secured to prevent tampering and unintended entry by either a lockable device or other approved method.
What is the minimum flow rate per outlet for nitrogen?
15 cfm
Medical gas and vacuum systems shall be capable of supplying the flow rates listed in Table 1305.2.
Listed flexible copper water connectors shall be installed in____________locations, unless
otherwise listed.
Readily accessible
Flexible water connectors shall be installed in readily accessible locations, and where under continuous pressure shall comply with ASME A112.8.6/CSA B125.6. Flexible water connectors with an excess flow shutoff device shall comply with CSA B125.5/APMO Z600.
What is the minimum distance between a gray water disposal field and a septic tank?
5 feet
No gray water system or part thereof shall be located on a lot other than the lot that is the site of the building or structure that discharges the gray water, nor shall a gray water system or part thereof be located at a point having less than the minimum distance indicated in Table 1503.4.
True or False: Where exhaust fans, clothes dryers and kitchen ventilation systems interfere with the operation of appliances, makeup air must be provided.
True
Where exhaust fans, clothes dryers, and kitchen ventilation systems interfere with the operation of appliances, makeup air shall be provided. [NFPA 54:9.3.1.5]
(NFPA 54: National Fuel Gas Code)
Floor-mounted fixtures must be rigidly secured to the drainage connection (and to the floor)by screws or bolts of:
Copper or copper alloy
Floor-outlet or floor-mounted fixtures shall be rigidly secured to the drainage connection and to the floor, where so designed, by screws or bolts of copper, copper alloy, or other equally corrosion-resistant material.
Where a fixture comes in contact with the wall or floor, the joint between the fixture and the wall or floor shall be made___________.
Watertight
When a fixture comes in contact with the wall or floor, the joint between the fixture and the wall or floor shall be made watertight.
After-coolers, dryers, receivers, and separators, must be equipped with:
Drains
Drains shall be installed on dryers, after-coolers, separators, and receivers.
Heat exchangers used for heat transfer, heat recovery, or solar heating shall protect the potable water system from being____________ by the heat transfer medium.
Contaminated
Heat exchangers used for heat transfer, heat recovery, or solar heating shall protect the potable water system from being contaminated by the heat-transfer medium. Single-wall heat exchangers used in indirect-fired water heaters shall meet the requirements of Section 505.4.1. Double-wall heat exchangers shall separate the potable water from the heat-transfer medium by providing a space between the two walls that are vented to the atmosphere.
Unless it can be demonstrated that the fire-resistive rating of the penetration is maintained, unshielded couplings may not be used to connect:
Noncombustible piping
Unshielded couplings shall not be used to connect noncombustible piping unless it is capable of being demonstrated that the fire-resistive integrity of the penetration is maintained.
Where can subsoil drains be piped to?
Alley, storm drain, street curb
Subsoil drains shall be piped to a storm drain, to an approved water course, to the front street curb or gutter, to an alley, or the discharge from the subsoil drains shall be conveyed to the alley by a concrete gutter. Where a continuously flowing spring or groundwater is encountered, subsoil drains shall be piped to a storm drain or an approved water course.
Where should medical gas and medical vacuum risers NOT be located?
Elevator shafts
Piping shall not be installed in kitchens, elevator shafts, elevator machine rooms, areas with open flames, electrical service equipment exceeding 600 volts, and areas prohibited under NFPA 70 except for the following locations:
(1) Room locations for medical air compressor supply systems and
medical-surgical vacuum pump supply systems.
(2) Room locations for secondary distribution circuit panels and breakers
having a voltage rating not exceeding 600 volts. [NFPA 99:5.1.10.11.3.2]
(NFPA 99: Health Care Facilities Code)
From the fixture outlet of a bar sink to the receptor, developed lengths may not be more than.
5 feet
Where the sink in a bar, soda fountain or counter is so located that the trap serving the sink cannot be vented, the sink drain shall discharge through an air gap or an air break (see Section
801.3.3)into an approved receptor that is vented. The developed length from the fixture outlet to the receptor shall not exceed 5 feet (1524 mm).