PCTs Flashcards
P-4
Rx tripped
2/2 Trip and bypass bkrs open or racked out
P-6
SR trip block
1/2 IR NIs >10^-10 A (5x10^-11 A)
Allows manual block of SR trip (auto unblocks)
P-7
Rx and Turb not at power
2/2 Both not at power
Auto blocks hi Lpzr, lo Ppzr, RCP speed, and RCS flow trips (auto unblocks)
P-8
3 loop
2/4 >50%
Enables lo flow trip on 1/4 loops (2/4 required <50%)
P-9
Rx trip on Turb trip
2/4 >51%
P-10
Rx at power
2/4 >11% (<9%)
Auto blocks SR trip and hi volts (auto unblocks if
P-11
Ppzr lo
2/3 <1992 (>2000)
Allows manual block of lo Ppzr and Pstm, inserts hi Beth rate MSI
(auto unblocks and opens SI accum valves)
P-12
Lo-lo Tave block
2/4 <553ºF
Auto blocks SDs (can be bypassed)
P-13
Turb not at power
1/2 (505/506) >10%
Feeds P-7
P-14
Hi-hi Lsg
2/4 on 1/4 >80%
Trips Turb, MFPs, FWI
P-19
Cold leg injection
2/4 < 1900#
Allows 8801s to auto open on SI
C-1
IR Hi Flux Rod Stop
1/2 >20% (current eq)
Blocks rod withdrawal (can be manually blocked >P-10)
C-2
PR Overpower Rod Stop
1/4 >103%
Blocks rod withdrawal
C-3
OT∆T
2/4 >119%
Blocks rod withdrawal, runback
C-4
OP∆T
2/4 >109%
Blocks rod withdrawal, runback
C-7
Load Reject
506 >10% step or 5%/min ramp decrease
Arms SDs (in Tave mode, manual reset)
C-9
Condenser Available
1/2 pumps/bay
3/3 <5” HgA
Allows SDs
C-16
Hi Terror/Lo Tave
Auction lo Tave >20ºF lo or <553ºF
Prevents Turb load increase (hold light)
C-20
AMSAC Not Armed
1/2 (505/506) <260# for >261 sec
SR Flux Hi Trip
1/2 >10^5 cps
Not credited
IR Flux Hi Trip
1/2 >25% (current eq)
Not credited
PR Flux Hi (Lo) Trip
2/4 > 25%
∆Sk too rapid for T/P
PR Flux Hi (Hi) Trip
2/4 >109%
Excessive heat flux leading to DNB
PR Flux Rate Hi Trip
2/4 +5 step ≤2 sec
Rod ejection
Manually reset
Lpzr Hi Trip
2/3 89%
Not credited
Overpressure (RCS)
Ppzr Hi Trip
2/4 >2385#
Overpressure (PZR and components)
Ppzr Lo Trip
2/4 <1900#
Limits OT∆T req’d range
OT∆T Trip
2/4 >120%
Slow DNB transients (stm blanketing)
Inputs: Tave, Ppzr, ∆I
OP∆T Trip
2/4 >110%
Not credited
Excessive kw/ft from SLB
Inputs: Tave, ∆T
Cannot increase
Lo RCP Speed Trip
2/4 <92.4%
Fast DNB transient
Lo Lsg Trip
2/4 in 1/4 <18%
DHR
Turb Tripped
4/4 TSVs closed
2/3 Pets <500#
Lo RCS Flow Trip
2/3 <90%
Fast DNB transient
P-8
Manual Rx Trip
1/2 MB4 or MB7
General Warning Trip
2/2 trains SSPS Trouble
11 conditions
First Outs contradict
N-1 Trip
> 1 loop sw/train bypassed
or
1 sw/train for different loops
SI
1/2 switches on MB2/MB4
2/3 >18#
2/4 <1892
2/3 in 1/4 <660#
Trips Rx, Turb, MFPs (14 sec TD)
CIA, FWI, CBI (man/18#)
Starts EDG, AFW, CHS, SI, RHR, SW, CCP, CAR, CRDM, AB Fans, EDG
60 sec to reset, P-4 blocks (train related)
CIA
1/2 PBs on MB2
SI
CIVs close (E-0 Att A) except CCP/CDS x-connects which open
CIB
2/2 on 1/2 sets of CDA PBs
2/4 >23#
Isolates CCP CIVs (45s, 48s, 49s)
CDA
2/2 on 1/2 sets on MB2
2/4 > 23#
Starts QSS, RSS, CHS, SI, RHR, AFW, SW HVK, IRR/CR ACUs
Stops CCP, CAR, CRDM fans
Energize to actuate
MSI
1/2 PBs on MB2/MB5
2/3 >18#
2/3 on 1/4 <660# or 100#/sec decrease
Close MSIV and bypasses, upstream traps, and ARVs
FWI
SI
P-14
P-4 and <564ºF
Close FRV and bypasses, CTV41s, and chem feed isolations
CBI
Manual SI
1/2 PBs on MB2/VP1
1/2 >1.5x10^-5 uCi/cc (or LOP)
2/3 >18#
CR to pressurized filtered recirc
TSC to filtered recirc
AFW
SI/CDA/LOP Lo Lsg (2/4 for TT)
Start AFW
Close sample and BDG isolations
AMSAC
1/1 in 3/4 ≤16% (>25 sec with C-20)
Trip Turb
Start all AFW
Close sample and BDG isolations
LOP
2/4 <70% (1.8 sec) and 1/1 <30%
2/4 <90% (4.5 min or 7.5 sec with SSS)
Slow transfer attempt for 5 sec
LOP signal to EGLS
Start signal to EDGs
CTMT Purge
1/1 ≥1R/hr
Close CTMT purge supply and exh