What plant chiller trips auto-restart?
Low chilled water flow 34” w.c. diff Low condenser flow 25” w.c. diff. Undervoltage Low oil temp (55°F reset @ 71°F) Low discharge temp 36°F
How long does the plant chiller oil pump run?
50 seconds prior to start
150 seconds after shutdown
If activated it Runs 10 minutes then auto stops if chiller is not running
How long after starting before chiller can be restarted?
30 minutes
What does plant chill water oil heater do?
115V heater maintain oil temp between 135°F and 145°F
What water supplies chilled water head tank?
P21 makeup water
What cools plant chill water?
PSW
What does the 2 primary pump feed?
3 secondary loops Aux steam tunnel Rad waste Rad waste control room CTMT penetration #83 (RWCU return)
What are the power supplies for plant chillers/
“A” 13AD
“B” 13AD
“C” 14AE
When will the standy primary chilled water pump auto start?
<77psig discharge pressure
What are 3 major loads of PCW?
Aux steam tunnel
Diesel rooms coolers (not tech spec required one)
Circ pump motor thrust bearing
What are the only valves that will isolate for PCW?
148, 149, 150 CTMT isolation
When will the PCW isolation valves isolate?
Group 6
Will PCW isolation valves cause a pump trip
No
What will be lost on CTMT/DW isolation of PCW?
CTMT Cooling