P44 Plant Service Water Flashcards

1
Q

What are the low flow trips for each well?

A
Well 1 <1600gpm or recirc <45% open
Well 3 <2000gpm or recirc <45% open
Well 4 <2000gpm or recirc not closed
Well 5 <2000gpm or recirc <45% open
Well 6 <1900gpm or recirc <45% open
*60 second time delay*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What are the low oil tank level trips for each well?

A

Well 1,3,4,5 <3.25”
Well 6 <3.1875”
60 second time delay

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What are the low well level trips for each well?

A
Well 1 - A no trip	B 7.7’
Well 3 - C no trip	D 6.2’
Well 4 - J no trip	K 6.5’ (30s TD)
Well 5 - E no trip 	F6.75’
Well 6 - L22.92’	M no trip (1m TD)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What will prevent ANY well pump from starting?

A
  1. Low well level
  2. Disconnect door open
  3. Main isolation switch (disconnect) open
  4. Motor thermal overload
  5. Power is not available
  6. Recirc and discharge valve not full closed (well 4 only)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What are the loads off the 12” secondary supply line?

A
Fire water storage tank
Turbine building sample panel backup
SJAE inter condenser
Mechanical vacuum pump jacket coolers
Makeup treatment clearwell tank
Circ water lube water
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What’s the loads off the 36” main supply line?

A
CRAC
CCW heat exchangers
Computer room coolers
Circ water 
SSW head tank 
ADHR
Drywell chillers
Plant chill water
ESF “A” and “B” switchgear room cooler
TBCW
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

If both pumps have been out of service for <24 hours, how long should you run a pump in recirc?

A

1 pump for 1 hour

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

If both pumps have been out of service for >24 hours, how long should you run a pump in recirc?

A

1 pump for 24 hours

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

How do louvers respond to fans starting and stopping?

A

When switch in ON they open/close with fan ON/OFF

When switch is OFF they remain current position

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What temp will trip the exhaust fans on “fire stat” thermal protection?

A

120°F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What are the power supplies for the radial well?

A

1,3,6 18AG

4,5 28AG

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Which pumps are located in each radial wells?

A
Well 1 A/B
Well 3 C/D
Well 4 J/K
Well 5 E/F
Well 6 L/M
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Where can PSW be discharged to after loads?

A

Circ pit or plant discharge basin

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

If plant load is increasing, what will TBCW TCV do? Is it concerned with PSW pressure?

A

Go open

No

How well did you know this?
1
Not at all
2
3
4
5
Perfectly