How does CO2 respond to auto initiation? Push button?
Alarm for 30 seconds then dump
CO2 How does it respond to manual initiation?
Dump immediately for set amount of time
P64 CO2 How many valves must be manipulated to initiate manually? Where are they?
1 at the tank
1 at the room
P64 CO2 How long should it be discharge manually?
Time listed on associated placard
P64 When do pumps Auto start/stop?
ON/OFF Jockey pump 135psig/147psig Motor driven 129psig/141psig (7min TD after start) Diesel driven “A” 123psig (5s TD)/Manual Diesel driven “B” 117psig (5s TD)/Manual
*diesel “A” and “B” will auto start on loss of control power after 15s TD)
What types of nozzles are on 208’ Aux building?
Stream only to prevent possible inadvertent criticality
What has manual deluge?
ANYTHING WITH A FILTER TRAIN Standby fresh air filter train SBGT filter train CTMT filter trains Post-accident filter train
What has automatic Deluge systems?
All transformers
Seal oil
RFPT Lube oil reservoir
Where are the dry pipe systems located?
Where freezing might occur
Turbine/Aux railroad bay
Chemical storage area
Where are the Auto pre-action deluges located?
Diesel generator rooms
Which CO2 systems have an abort switch?
Remote shutdown room
Upper and lower cable spreading room