NEW Flashcards
Operating Error - East River
.
Operating Error - Cherry St
.
Operating Error - West 42nd
.
0400-0400
PSMP
- Compliance with NERC Standard PRC005-6
- PM of protection system elements:
- Protective relays
- Communication systems
- V/I sensing devices
- Station DC supply
- DC control circuitry
- Time-based maintenance program for BES protection
- PSMP maintenance intervals meet or exceed NERC requirements
- Maximo asset and work management software to schedule/track time-based maintenance (listed by zone of protection)
0400-0400
PM Frequency
Protective BES Microprocessor Relay – 6 years
(analog-to-digital, settings, I/O)
Protective BES Non-Microprocessor Relay – 4 years
(Calibrate following Protest test plans, relay manufacturer, 0400 instructions)
Communication Systems – 4 years, 12 years
(Operational tests)
CT/PT – Same interval as protective relay
In service/Out of service (CT SAT)
DC Control Circuitry – 4 years (BES)/6 years (non-BES)
Trip checks
Station DC Supply – 4 months/18 months (SSM/Station Operators)
Supply voltage, etc
Alarm Paths – 12 years
UFLS – 12 years
0400-0205
Microprocessor Relay Maintenance and Testing
- Equipment: Protection Suite, Microprocessor Relay Maintenance Form, laptop, relay software, Doble Test Set, multimeter, cables
Before testing: Provide proper isolation, PST awareness checklist checked off, work permit, schematics
- Verify I/O
- Metering check: verify analog-to-digital converter (inject balanced I/V, compare to metered values of relay, verify CT/PT ratios)
- Verify relay settings, time/date
- Verify passwords
- Force output contact/verify input contact
0400-0347
Testing Electric Circuits
- Required at new installation or where modifications have taken place
AC:
- Point-to-point wire checks: buzzer
- Insulation resistance: use megger (high V, low I), disconnect form ground, apply V. Minimum is CE-ES-1002
DC (control, power, alarm, Sequence of Event Recorders, oscillograph, annunciator):
- Insulation resistance
- Operational
- Polarity (oscillograph inputs)
0400-0402
Testing Guidelines for Commissioning Equipment
AC
- Wire checks
- Insulation resistance
- Circulating current (read with phase angle meter)
- Primary injection
- Load readings (phase angle meter)
DC
- Trip/operational
- Insulation resistance
Relays
- Test plans, I/O, analog-to-digital
CT/PT
CT: Ratio, polarity, insulation resistance, saturation (CT)
PT: ratio, polarity
Communication Circuits, Alarms, Indications
0400-0345
Performing Trip and Operational Tests at Area Substations
- Isolate
- Local trip tests/full trip test
- Verify breaker failure timers
- Transfer trip
- AGS/CS
0400-0437
Startup/shutdown trips
0400-0401
Guidelines for Primary Injection Testing
Unbalanced/balanced
0400-0108
Testing Multi-Contact Auxiliary Relays
- Self reset, manual reset, electrical reset
- Insulation resistance, mechanical inspection, trip/reset coil R, minimum pickup, operating times
Etc.
0400-0316
Working Near Electrical Equipment in Substations
- Isolate from all sources of supply (including backfeed) before testing
- Adequate clearance: Blue Book
- When working on in-service equipment, discuss possibility of inadvertent trip out with operator
Before signing Work Permit, verify that protection has been provided by Substation Operator
0300-0030
Types of permits
Work Permits and Test Permits
Work permit: Permission granted to permit work or test on equipment. Verbal may be issued to PST for in-service work
Test permit: Permission for employees not normally working in substations to apply V to dead equipment
Electrical permit: work on electrical equipment
Mechanical permit: steam/water/oil/insulating or dielectric fluid, etc
Area permit: area where structural, construction, alteration, excavation or demolition work
Authorized Employee
A person certified by department manager as meeting minimum requirement to hold work or test permit.
Maintained in SSO website
0300-0030