MTA CAMS PRDC Fire Detection and alarm system Signals (Dedicated function system) Flashcards

1
Q

What type of fire alarm system is required for signal FA systems ?

A

an addressable FA system

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What are some areas that will be included in this FA system ?

A

relay rooms
central instrument rooms

and train controls

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

what must occur during the change in fire alarm systems?

A

fire watch must occur

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is a another option that the design–builder can consider doing besides replacing the Signal FA system ?

A

Alternatively, the Design-Builder may elect to utilize the existing signals fire alarm system provided that it can be expanded to meet the requirements of this section without resulting in an impairment to existing signals areas that must be protected during construction

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

For new signals areas located within the stations under the Contract what should be done ?

A

connect the new signals fire alarm system to the existing station FACP for monitoring at the agent booth location

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What are some actions required to be done on new signals areas

A

upgrade, replacement, programming and testing

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

if the signal FA system is not able to connect to the main FACP what should be done

A

a remote annunciator should placed in the agent booth that is connected to the signal FA system

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What must be done in order to have a remote annunciator for a signal FA system in place of connecting it to the main FACP

A

request document must be sent to the project CEO outlining that that the alarm system is not able to be expanded

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Where will normally occupied stand alone signals buildings have their remote annunciators installed if they are required

A

in the maintenance supervisor office

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

If a signals area is located within a station that is already controlled by a full station alarm system what must occur when implementing the station alarm system

A

The existing Fire alarm system notification devices will be extended into the signal areas effected

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What will happen if their is a fire in the signals area that has notification devices connect to a existing full station alarm system that also has a signal alarm system

A

the alert the notification devices will only the existing full station alarm system and not the signal alarm system

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What will happen in the event that an alarm occurrence is activated in the the signal alarm system and how will this action be done

A

An activation of the signal alarm system shall not result in the activation of the station fire alarm appliances

this will be done using signal modules on a room by room basis

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Were should the fire alarm panels for signals be placed

A

either in the fire suppression room for releasing systems or in the relay room if installations do not include clean agent protection.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is the only thing that the FA panels for the signal room should protect

A

it should only protect signal related rooms

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is a clean agent ?

A

A clean agent is a fire extinguishing agent that is volatile, gaseous, or electrically non-conductive. It does not leave a residue when it evaporates.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What type of enclosure should the fire alarm panel be placed in ?

A

NEMA 4X

17
Q

How will the signal alarm panel show the status of its alarms and what will these statuses be

A

The signal alarm panel will use LED indicators to show the statuses of alarm, normal and reverse status, abort active and zone discharge state

18
Q

all fire alarm conduits shall adhere to

A

PRDC6.11.3E raceways

19
Q

The final connections to interfaced equipment shall be

A

flexible non-metallic 3 feet max length

20
Q

What dictates the specs for mounting and box fill for back boxes

A

the manufacturer

21
Q

what type of cable is used for connecting to operational networks for the existing CAMS

A

cat 6

22
Q

all provisioning and installation should be done except for

A

head end configuration to CAMS

22
Q

what class of circuit should be used for notification

A

class B

22
Q

what class of circuit should be used for signaling/ data

A

class X with isolators every 50 devices

22
Q

what class of circuit should be used for Auxilary/controls

A

Class B for mechanical and releasing appliances

23
Q

What level of pathway survivability is needed for fire alarm circuits

A

none

23
Q

Were should smoke alarms be located

A
23
Q
A
23
Q
A
24
Q
A
24
Q
A
24
Q
A
25
Q
A