What type of fire alarm system is required for signal FA systems ?
an addressable FA system
What are some areas that will be included in this FA system ?
relay rooms
central instrument rooms
and train controls
what must occur during the change in fire alarm systems?
fire watch must occur
What is a another option that the design–builder can consider doing besides replacing the Signal FA system ?
Alternatively, the Design-Builder may elect to utilize the existing signals fire alarm system provided that it can be expanded to meet the requirements of this section without resulting in an impairment to existing signals areas that must be protected during construction
For new signals areas located within the stations under the Contract what should be done ?
connect the new signals fire alarm system to the existing station FACP for monitoring at the agent booth location
What are some actions required to be done on new signals areas
upgrade, replacement, programming and testing
if the signal FA system is not able to connect to the main FACP what should be done
a remote annunciator should placed in the agent booth that is connected to the signal FA system
What must be done in order to have a remote annunciator for a signal FA system in place of connecting it to the main FACP
request document must be sent to the project CEO outlining that that the alarm system is not able to be expanded
Where will normally occupied stand alone signals buildings have their remote annunciators installed if they are required
in the maintenance supervisor office
If a signals area is located within a station that is already controlled by a full station alarm system what must occur when implementing the station alarm system
The existing Fire alarm system notification devices will be extended into the signal areas effected
What will happen if their is a fire in the signals area that has notification devices connect to a existing full station alarm system that also has a signal alarm system
the alert the notification devices will only the existing full station alarm system and not the signal alarm system
What will happen in the event that an alarm occurrence is activated in the the signal alarm system and how will this action be done
An activation of the signal alarm system shall not result in the activation of the station fire alarm appliances
this will be done using signal modules on a room by room basis
Were should the fire alarm panels for signals be placed
either in the fire suppression room for releasing systems or in the relay room if installations do not include clean agent protection.
What is the only thing that the FA panels for the signal room should protect
it should only protect signal related rooms
What is a clean agent ?
A clean agent is a fire extinguishing agent that is volatile, gaseous, or electrically non-conductive. It does not leave a residue when it evaporates.
What type of enclosure should the fire alarm panel be placed in ?
NEMA 4X
How will the signal alarm panel show the status of its alarms and what will these statuses be
The signal alarm panel will use LED indicators to show the statuses of alarm, normal and reverse status, abort active and zone discharge state
all fire alarm conduits shall adhere to
PRDC6.11.3E raceways
The final connections to interfaced equipment shall be
flexible non-metallic 3 feet max length
What dictates the specs for mounting and box fill for back boxes
the manufacturer
what type of cable is used for connecting to operational networks for the existing CAMS
cat 6
all provisioning and installation should be done except for
head end configuration to CAMS
what class of circuit should be used for notification
class B
what class of circuit should be used for signaling/ data
class X with isolators every 50 devices
what class of circuit should be used for Auxilary/controls
Class B for mechanical and releasing appliances
What level of pathway survivability is needed for fire alarm circuits
none
Were should smoke alarms be located