existing fire alarm system shall be replaced by……
an addressable fire alarm system
The escalator FA system should be connected to the
Existing station FACP
Where should the FACP be located?
the agent booth
How long must fire watch be conducted?
I should conducted for the duration of the fire alarm installation
What could also be used for monitoring of the elevator F.A system in the event that expansion from the FA panel is deemed unfeasible due to Fa system obsolesence or field conditions?
using a dedicated remote annunciator for the elevator/ escalator FA system
IF a remote annunciator is required where should it be located ?
In the agent booth
The FIRE alarm panel for elevators and escalators should be placed in a…..
Nema 4x enclosure
FACP for elevator and escalator should be placed in the…..
elevator machine room
What should never be placed in the elevator machine room FACP
any non elevator escalator associated equipment
IF their is no fire alarm panel in the station where it the FACP for the elevators an escalators allowed to be?
in the full time control area
What will be the designation of the elevator escalator FACP if it is located in the main control area?
elevator and escalator control expandable for general station protection.
If the elevator/escalator FA system requires a remote annunciator what type of enclosure does it required
NEMA 4X
What specifications should all conduits in the project abide by
PRDC 6.11.3E Raceways
What are the 3 requirements for final connections for interfaced equipment ?
They must be
1. flexible
2.non-metallic conduits with a 3.max length of 3 feet
What determines the box fill and mounting of the devices back boxes?
The manufacturer
what type of wire should connect the local application node to the operational network for existing CAMS?
A CAT 6 cable
What is Lift-NET ?
A monitoring tech for elevators and escalators
All sprinkler application for escalators are required to have distinct relay based inputs to the escalator controller, what are these applications ?
a. Sprinkler water sensor indication- for each water sensor
b. Sprinkler heat trace system fault- as a common alarm point
c. Sprinkler tamper switch off normal, grouped common alarm point by location of valves (i.e. - water meter room, EMR).
Each sprinkler water sensor indicator is required to have
relay based inputs
What is a relay input ?
A relay input is the part of a relay’s frame that connects to the control component. The input circuit activates when a voltage higher than the relay’s specified pickup voltage is applied to the input.
What type of installation is not permitted for escalator/ elevator fire alarm systems ?
head end configurations to CAMS
what is a head end system ?
Head end systems are systems that collect measurement data and meter events for eventual submission to the application. Many devices can communicate to the application through a single head-end system, but a utility may have numerous head-end systems through which they communicate with devices.