MTA CAMS PRDC Fire Detection and alarm system back house Flashcards
existing fire alarm system shall be replaced by……
an addressable fire alarm system
What are the two main features of an addressable fire alarm system?
- All pieces of Equipment must be connected with each other as well as the main Fire alarm panel
- Each piece of equipment must be given a specific identification unique to them
What must occur during the replacement of a fire alarm system?
Fire watch will be established for the duration of a fire alarm system replacement or modification
What is a fire watch ?
A fire watch is the continuous patrol of a location to monitor for evidence of fire, smoke or any abnormalities
Stations that utilize
__________ and _______________ fire alarm systems may expand for station _______________ and ______________
Edwards EST-3 and Simplex 4100ES
back of house coverage and elevator control
what type of fire alarm panel will no longer be used for station or elevator protection?
Any fire alarm panels that reside in or protect signal areas
What can fire alarm panels in signal areas be used for?
The can be used by the new fire alarm system for monitoring used only.
What must be done to the existing fire alarm system after installation of the addressable fire alarm system ?
They must all be connected in such a way that the addressable fire alarm system can monitor the existing fire alarm system.
What protocol must introduced into an existing fire alarm system that protects back of house and administrative areas ?
for two-way cross alarming
What is cross-alarming ?
Cross-zone detection is all about the confirmation of a fire through requiring two fire detectors in the space to activate before beginning the releasing sequence. Cross-zoned detection is not always used to release a suppression system, but it often is when using smoke detectors
When cross-alarming is intruded what should the system avoid ?
the system should avoid re-transmission of an alarm signal back to the originating system.
If an existing system is not able to intact cross-alarm due to obsolescence, technical inability, or state of disrepair of equipment what must happen to the system ?
the Design-Builder shall remove the affected existing system or systems and associated conduit, patch and restore the area to match surrounding area, and incorporate the required fire alarm protection onto the new fire alarm system.
What types of panels should be avoided when intruding cross-alarming ?
fire alarm panel that resides or protects signal area
What change will be made to function elevator, escalator and signals fire alarm systems that remain after fire system modification or replacement ?
They will have their general alarm notification appliances removed and replaced with those connected to the station panel.
What should be done to all new system and modified existing system ?
They must all go through programming installation and re-testing
What type of enclosure must be used for fire alarm panels in and around the control area ?
NEMA-4X
How should a fire alarm panel be mounted?
it should be surface mounted
When addressing the degree at which a panel is projected from the wall, what requirements must be meet ?
ADA requirements
What type of enclosure should notification appliance extender panels be given ?
NEMA-4X
What is a notification appliance extender ?
a two wire circuit with a resistor that can be found at the fire alarm panel. It extends power to notification appliances such as bells, horns, chimes, speakers, and strobes.
What device besides the FACP panel should be placed in the agent booth ?
Thee remote annunciator
What is a remote annunciator ?
Remote annunciators are smaller panels that provide a fire system status and a limited set of functional switches
What must be done it the stations remote annunciator is not in the full time control areas ?
a second remote annunciator must be placed in the control area
What type of enclosure must the second remote annunciator be given ?
NEMA-4X
What specifications should all conduits in the project abide by
PRDC 6.11.3E Raceways
What are the 3 requirements for final connections for interfaced equipment ?
They must be
1. flexible
2.non-metallic conduits with a 3.max length of 3 feet
What determines the box fill and mounting of the devices back boxes?
The manufacturer
Final terminations to sprinklers are allowed to be ……..
flexible non-metallic conduits
what type of wire should connect the local application node to the operational network for existing CAMS?
A CAT 6 cable
What type of alarm circuit is allowed for signaling and data ?
Class X
Under what parameters is a class B pathway allowed to be used in signal/data circuit?
If the circuit is used for specific elevators or escalator banks.
What type of alarm circuit is allowed for Notification ?
Class B
What type of alarm circuit is allowed for Auxiliary/Controls?
Class B
What are the requirements for a Class B circuit used for Auxiliary/Controls for a escalators ?
Each escalators must have a dedicated class solenoid release circuit
What are requirements of the pathway survivability of a fire alarm circuit ?
None