Mode 3 to Mode 5 Flashcards
Describe the scope of 40OP-9ZZ10 Mode 3 to Mode 5 operations
- Stabilizes the plant in Mode 3 to set up for cooldown or start-up
- Plant cool down to Mode 5.
- Secondary plant shutdown while using the EOP
State the precaution associated with RCS heat addition or removal methods.
- Changes to RCS heat addition or removal methods (RCPs, SGs and ADV/SBCS, etc.) should be made by only one method at a time and sufficient time allowed for accurate indication temperature change before making the adjustment.
State the precautions associated with performing dilutions while subcritical.
- Anticipate criticality for any dilutions
- Stop dilutions if power / count rate doubles
- EOL: large dilutions required to achieve Estimated Critical Boron Concentration (ECBC).
- Dilution is allowed to start as long as final Cb is maintain 50 ppm > ECBC or 50 ppm > SDM Cb.
State when PZR boron equalization is required to be performed.
- RCS/PZR boron equalization started if RCS boron changed by 50 ppm. Maintain ≤ 10 ppm difference.
What is the SDM boron concentration admin limit and why is it in place?
- Admin boron limit is maintain 100 ppm above required SDM boron.
- Compensates for changes in NCW / letdown temperatures
State the auto features associated with PZR level temperature compensation.
- LT-110X/110Y (hot cal) / LT-103 (cold cal) PZR level
- LT-110X/Y: if colder than 653°F/2250 psia, indicated will be higher than actual (swaps < 20%)
- LT 103: if hotter than 60°F/14.7 psia, indicated will be lower than actual (swaps < 20%)
WHen is LTOP required to be placed in service?
- LTOP required when any Tcold is ≤ 221°F (Both SDC suction relief valves in-service)
State the temperature requirements associated with SDC:
- SDC design limit:
- LPSI pump seal temperature limit:
- Extended SDC operations temperature limit:
- CS pump to SDC temperature/pressure limits:
- 350°F – SDC design temperature limit (FSAR)
- To extend LPSI Pump seal life, SDC normally initiated when RCS is < 300°F. (SM permission to align > 300°F)
- Extended SDC ops (> 4 days), should be performed at ≤ 135°F
- CSP cannot be aligned to SDC until ≤ 200°F / ≤ 250 psia. (Limits prevent pump damage.)
What is a concern when venting from penetration rooms when in midloop conditions?
Venting may introduce air into SDC System.
State the CHP pulsation dampener precharge pressure limitations.
- Charging Pump pulsation dampener precharge pressure should be maintained at ~ 60% of charging operating pressure and will always be maintained at 25-75% of charging system pressure.
State the requirements of LCO 3.6.6 CS system.
- LCO 3.6.6 requires both trains of CS to be operable Modes 1-4 ≥ 385 psia.
- One train of CS is required to be available until Mode 5 entry (PRA requirement)
- Due to not having class CTMT HVAC. LOCA in Mode 4 < 385 psia may not be covered.
Why are generator PCBs limited to 2 hours of being energized and open?
-
Generator PCBs (935/938) should not be open and energized for > 2 hours.
- Reduces life or causes premature break down of the surge capacitors which are shunted to the breaker contacts.
- Reclose for SWYD reliability (ring bus)
- U1: Switching may cause a drop in voltage (3kV). If SIAS present, it could load shed WRF.
What could occur if RCS pressure is lowered below the shutoff head of the RMW pump?
- ↓ RCS pressure below shutoff head of RMW pump may allow an uncontrolled dilution of the RCS.
State the max amperage to the following MFW pumps:
AFA:
AFB:
AFN:
It’s steam driven…
151 amps
122 amps
What is a consequence of extended use of AFNP01 when SG lvl is < 27% NR?
How is this avoided?
- Extended use of AFW to maintain ≤ 27% NR may damage the downcomer feed ring and piping. Lines become voided < 27%. Minimize voiding and water hammer.
- Feed ≥ 250 gpm until > 27% NR
- < 250 gpm – potential water hammer