Metro SOG 06 - Sheet1 Flashcards
From Metro SOGs:
What are the two methods that can be used to operate the fans and dampers ?
remotely at OCC, at the local fan control panels near each fan
From Metro SOGs:
In which mode can OCC override the the thermostatic controls and control fan shafts remotely?
Automatic mode
From Metro SOGs:
What color light will be lit at the local fans control panels if the panel is a the automatic mode? What light will be on if they are placed in Emergency Supply/Exhaust?
Green light = Automatic / Red Light = Emergency Supply/Exhaust / OFF = No Light
From Metro SOGs:
In which mode will be fans to move air OUT of the tunnel or station? In which mode will move air IN to the tunnel or station?
Emergency Exhaust = OUT / Emergency Supply = IN
From Metro SOGs:
When controlling ventilation OCC can only control fans at the supervisory control console if the local control switches are in what mode?
Automatic mode. OCC cannot control the fans if they are removed placed into Emergency Supply/Exhaust or Off.
From Metro SOGs:
During an extrication operation what must be monitored? What is an excellent unit for this task?
Air Monitoring and The Haz-Mat Unit
From Metro SOGs:
In which mode will be the UPE and fan shafts in the tunnels at both ends of the platform be placed in during a fire at the PLATFORM LEVEL?
Emergency Exhaust to push the smoke out of the fan shafts and pull fresh air in the escalators to protect egress and access.
From Metro SOGs:
Which mode will the UPE and fan shafts in the tunnels at both ends of the platform be placed in when there is fire at the MEZZANINE LEVEL?
Supply mode, pushing the smoke and heat up the escalators and out. This protects the passengers on the platform level whom can then be evacuated by train to another station.
From Metro SOGs:
During a fire on the Mezzanine Level, if the escalators are blocked as a means of egress but the platform is clear, what is the primary means of evacuation?
A train can transport passengers from the affected station to the next
From Metro SOGs:
In the event of a tunnel fire not located under a fan shaft what shall occur? What is this effect called?
The fan shaft on one side of the fire will be placed in supply while the other is placed in exhaust and all dampers to ventilation shafts nearby are closed. This effect is called the “Push Pull” effect.
From Metro SOGs:
What two modes are acceptable on a local fan control panel when ENTERING a Metro Fan Shaft? What mode would FD personnel never enter?
Should be placed in Manual Supply or OFF. FD Personnel shall never enter a Fan Shaft in Exhaust mode.
From Metro SOGs:
In Normal Operation, fans and dampers operate automatically by a thermostat when _______?
the preselected temperatures are reached
From Metro SOGs:
What are the four options on a local control panel in a Metro Fan Shaft?
- Automatic (OCC can control remotely, otherwise operated by thermostats) 2. Emergency Supply 3. Emergency Exhaust 4. Off (Some panels will not have this option)
From Metro SOGs:
What four things will a properly coordinated ventilation effort do?
- Establish a constant direction of airflow 2. Move the Smoke and Heat away from attacking firefighters and exiting passengers 3. Confine the heat and smoke to a limited area 4. Facilitate fire extinguishment
From Metro SOGs:
In addition to the Fans, Dampers, and Thermostats what action also circulates air in a Metro Station? What should the IC take into consideration?
Train Movement = The Piston Action /These air blasts should be taken into consideration by the IC when Metro wants to move trains near an incident.