Loss of Loadcenter Flashcards
What are major actions for loss of B-1?
1) If A MFP in service and not maintaining properly, then Trip it and perform Loss of SG feed.
2) Check systems started appropriately (ICW, CRD Pump, MFP lube oil pumps, P-6A Running)
What major actions are performed for loss B-2?
1) Perform loss of ICW in conjunction
2) If all ICW pumps off, then trip rx and trip RCPs due to loss of motor cooling, RT-5.
3) If B MFP not maintaining flows, then open crosstie valve and trip B MFP
What are major components powered from B-1?
What major components are powered from B-2?
What are major actions for loss of B-3?
1) Ensure proper equipment running (C-5B, P-14B EH Oil, Isophase, IA Compressor)
2) Align xfmr cooling supply from B-4
What are major actions for loss of B-4?
1) Ensure proper equipment running (Vacuum pump, EH pump, Isophase, IA Compressor)
2) Align xfmr cooling to B-3
3) TRM for FO Vault fire detection
What are major actions for loss of B-5?
1) Select B56 to B-6
2) Ensure EDG running with output breaker closed, A-309 open, service water pump running on A3
3) If OP HPI pump tripped isolate Letdown
4) If B5 cannot be energized, Place EDG output breaker in PTL, Diesel in lockout, close SW crossties to maximize flow to operable diesel
5) Begin plant shutdown and cooldown
6) If B5 was re-energized, shutdown EDG and restart OP HPI pump
7) Realign HPI
What are major actions for Loss of B-6?
1) Select B55/56 to B-5
2) Isolate Letdown
3) Throttle open TGLO and Gen H2 valve (Loss of Y02 causes them to close)
4) Close CV-1206
5) Ensure #2 EDG running and output breaker closed
6) If B6 cannot be energized, secure EDG and begin plant SD/CD.
7) If B6, not energized then use ES stby HPI Pump with suction from BWST as necessary for RCS makeup.
What are major actions for loss of B7?
Ensure ICW booster pump bypass valve opens
What are major actions for loss of A1?
1) Trip Rx
2) If OP HPI stopped, isolate LD, Trip RCPs, perform Loss reactor coolant makeup and RT-5
3) Trip A MFP
4) Ensure DG1 starts and ties on with SW pump running
5) Address systems (ICW, Cond Vacuum, IA, Condensate transfer, P-6B, chill water, sf cooling
What are major actions for loss of A-2?
1) Trip Rx
2) Isolate LD with LD cooler outlets
3) If OP HPI pump stopped, trip all RCPs and perform loss of reactor coolant makeup, RT-5
4) TRIP B MFP
5) DG running supplying bus with SW Pump running
6) Perform Loss ICW in conjunction (down to 1 ICW pump)
7) Address MISC systems (Condenser vacuum, IA, chill water, SF Cooling, condensate transfer)
8) If Y02 de-energized manually open TGLO and GEN H2 valves
What circumstances require trip or the reactor?
1) Loss of A-2, A-1
2) Loss of B-2 and unable to open MFP crosstie
3) Loss of all ICW pumps