LM2500 Module Parameters Flashcards
1
Q
Cooling Fan LP Alarm
A
3” H2O Across Fan
2
Q
Icing Alarm
A
41 F / 70% Humidity
3
Q
Heater Rating
A
8KW
4
Q
Heater On
A
60-70 F
5
Q
Heater Off
A
85-95 F
6
Q
Heater Blower On
A
120-130 F
7
Q
Heater Blower Off
A
145 F
8
Q
Cooling Air Outlet Temp High Alarm
A
350 F
9
Q
Enclosure Temp High Alarm
A
400F
10
Q
Colling Fan/Damper Automatic Operation
A
Vent Damper shuts when outside air temp <70F w/GTM off for 10 min
11
Q
Fire resistance
A
200 F for 15 Min
12
Q
UV Light Flame Detectors
A
1900-2100 Angstrom Range
13
Q
Halon Bottles
A
1 Per GTM - 95lb Bottle w/600 PSIG N2 (1 95lb in STBY)
14
Q
Bottle Rupture Disc
A
Vent to Space (Not GTM) at 2650 PSIG (240F)
15
Q
CO2 Actuation cylinder
A
2 Per GTM - 5 lb, 850 psig at 70 F w/ 30 sec time delay