Kahoot/ThingsTimSaid Flashcards
What are the three parts of fire protection.
- ) Detection
- ) Suppression
- ) Containment
When was the first smoke detector manufactured (for commercial use)?
1960
What was/is the main purpose of fire alarm systems?
Life safety of occupants.
What is a proprietary system?
A system that only protects the buildings in which they own.
Give the three main functions of a FA control panel.
- ) Receive alarm signals from initiation devices
- ) Send output signals to NAC circuits
- ) Monitor SLC and NAC circuits for integrity.
IDC and NAC circuits monitor for integrity how?
They have a slight current with an end of line resistor, when the current doesn’t flow, a trouble is reported. In an IDC circuit, if the resistance is no longer seen because of a short, an alarm is reported.
How far from the ceiling must wall-mounted heats be mounted?
Between 4” and 12”. No less than 4, no more than 12.
What is the difference between proprietary and remote monitoring stations?
Proprietary are only buildings owned by the same owner.
Remote is a third-party monitor.
A device with inputs and outputs that also monitors for troubles is a basic description of ____.
A fire alarm control panel.
What does a trouble indicate?
That system integrity is poor. i/e ground fault, open connection, removed device, etc.
Where are trouble signals generated?
At the FACP. (Control Panel)
Which of the fire alarm circuit types is used to poll devices?
SLC
Why doesn’t the slight current for monitoring a NAC circuit operate the horns/strobes/etc?
Because when in alarm, the polarity reverses, and the devices are made to operate only on reverse polarity.
What is the lowest temperature we are permitted to install FA equipment in?
32 Degrees Farenheit
Why is t-tapping not allowed on IDC or NAC circuits?
Because if a t-tapped device is removed or disconnected, the EOL resistor is still seen by the control panel and no trouble signal is given.
What is special about class A fire alarm circuits?
They require redundant return paths for single-break monitoring.
What type of circuits are door magnets considered?
Class D
Can the circuit feeding a fire alarm panel be shared with lights/receptacles?
No
What are the three main signals in fire alarm systems?
- ) Alarm
- ) Trouble
- ) Supervisory
Tampers initiate a _____ signal.
Supervisory.
Most duct smokes are wired/programmed to give ____ signals, this is to mitigate nuisance alarms.
Supervisory.
T/F: All devices on SLC circuits have unique addresses.
True.
What is the highest temperature we’re permitted to install FA equipment in?
120 degrees Farenheit
Anyone installing fire alarm systems should be ____ and ____.
Licensed and Experienced.
All initiating devices can be thought of simply as ____.
Switches.
Smooth ceiling spacing for HEAT detectors is ?
50 Feet
At least how far from heating vents must smoke detectors be?
3 Feet
T/F: Combination Horn/Strobes can be wired on the same circuit.
True.
T/F: Speaker/Strobes can be wired on the same circuit.
False.
Audible wall mounted notification appliances must be mounted ____ from the floor but no less than ____ from the ceiling.
90”, 6”
Combination wall mounted horn strobes must be mounted so that the lens is between ____ and ____ from the floor.
80-96”
Corridor strobes must be mounted so that they’re no farther than ____ from the end of the corridor.
15’
Some fire codes require the use of a ____ instead of Fire-Fighter’s telephones.
DAS (Distributed Antenna System)
The inside of a conduit installed in a concrete slab is considered a ___ location.
Wet
Generally speaking, power limited FA circuits operate at ____ or less.
100 VA
Which cable type is rated for plenums?
a. ) FLP
b. )FPLP
c. ) FLC
d. ) PCV
a.) FPLP
Non-power limited circuits operate at voltages up to ____.
600V
Poor workmanship will cause which of the following?
a. ) Nuisance Alarms
b. ) System Failure
c. ) Ground Faults
d. ) All of the above
d.) All of the above.
Power-limited circuits may be wired using which of the following methods?
a. ) Chapter 3 Wiring Methods
b. ) Non-power limited wiring methods
c. ) Power-limited wiring methods
d. ) All of the above
d.) all of the above
The actuation of a fire suppression hood in a kitchen must initiate a(n) ____ signal.
Alarm
In elevator hoistways and machine rooms, heat detectors must be installed within ____ of every sprinkler head.
2’ or 24”
HVAC systems must be shut down when fans are ____ cfm or more.
2000.
Door magnets are:
a. ) An emergency control function
b. ) An example of containment
c. ) Installed on a class D, fail-safe circuit
d. ) All of the above.
d.) all of the above.
T/F: High-rise stairwells are pressurized so that smoke cannot enter it.
True
Control relays must be installed within ____ of the components they control.
3 Feet.
What does PIV stand for?
“Post Indicator Valve”
In building Mass Notification Systems (MNS) provide ____
a. ) Radio enhancement
b. ) Two-way communication
c. ) Voice instructions for a life-threatening emergency
d. ) Lunch
c.) Voice instructions for a life threatening emergency.
An EVACS system uses _____ communication.
a. ) Multi-party
b. ) One-way
c. ) Two-way
d. ) All of the above
b.) One-way communication
A fire command center (FCC) is ____
a. ) Where firefighters begin response to a fire
b. ) Contains fire alarm system controls
c. ) Must have a 3 foot clearance around equipment
d. ) All of the above
d.) All of the above
A temporal 3 signal is used for:
a. ) Standard evacuation
b. ) Voice instructions
c. ) Assist firefighters to area
d. ) Coded signals
a.) Standard evacuation
circuits required to meet survivability requirements must be protected from fire for at least ____.
2 hours
EVAC systems utilize what kind of device?
Speakers
Fire alarm specifications are enforced by who?
The Designer
The smallest size drawing you can get is size _____, or 8&1/2 X 11”
Size A
Record (as-built) drawings are made by _____.
The installing contractor.
_____ drawings are where you will find fire barriers and fire rated walls.
Life safety.
Which of the following documentation must be provided for all fire alarm system installations?
a. ) Calculations
b. ) Floor plans
c. ) Riser diagrams
d. ) All of the above
d.) All of the above
What are the three sides of the fire triangle?
Oxygen, Ignition, Fuel.
What kind of detector is most appropriate for high ceilings such as an atrium?
Projected beam-type smoke detector.
HVAC systems of _____ cfm or greater require fan shutdown when the fire alarm is activated.
2,000
Which of the following is an example of a smoke control function?
a. ) Elevator recall
b. ) Door unlocking
c. ) Stair pressurization
d. All of the above
c.) Stair Pressurization
Door release service is used to?
a. ) Close doors when smoke is detected
b. ) Maintain fire rated corridors
c. ) Control the spread of smoke
d. ) All of the above
d.) All of the above
T/F: Door magnets can be powered by the fire alarm panel or a separate power source.
True
What type of drawing contains details necessary to install a fire alarm system?
Shop Drawings
NFPA 72 requires all equipment used in conformity with the Code to be ____ for the purpose for which it is used.
Listed
AIM stands for _____
Addressable Input Module
AOM stands for ____
Addressable Output Module
What year was the first operational public emergency alarm reporting system installed?
1852
Central and subsidiary stations have which of the following?
a. ) Runner service for protected premises
b. ) Maintenance services for the protected premises
c. ) strict requirements for their facilities
d. ) All of the above
d.) All of the above
Central station supervising service provides ___ elements of service.
6
T/F: Remote supervising stations serve properties under various ownership and can be provided by a central station
True
___ are owned and operated by the owner of the protected premises and may not monitor property owned by others.
Proprietary supervising stations
The digital alarm communicator system (DACS) transmitter ____
a. ) Is the most widely used means of transmitting fire alarm data
b. ) Uses a loop start telephone line
c. ) Must have a second means of transmission
d. ) All the above
d.) All of the above
Single and multiple station household alarms are required in what type of occupancies?
Dwelling spaces such as apartments, hotel rooms, dorms, etc.
T/F: The fire alarm in one dwelling can cause alarms in another dwelling.
False.
Wall mounted heat detectors must be mounted so the top of the detector is between ____ and ____ inches from the ceiling.
4-12”
What is the maximum number of un-monitored smoke alarms that can be interconnected?
12 smoke alarms
Smoke detectors or alarms must be located at least ____ from a supply diffuser or tips of a paddle fan.
3 Feet
Audible notification from single station and multiple station smoke alarms must sound for at least ____ minutes
4
T/F: A re-acceptance test is required after making changes to a fire alarm system.
True
Who is responsible for proper maintenance and testing of the fire alarm system?
The owner.
Ground faults occur when ____
One of the circuit conductors is grounded.
In most cases, a short on a class B initiating device circuit causes a(n) ____ signal.
Alarm
T/F: Improperly connected or grounded shields often result in erratic operation.
True.
Removal of a device off of the NAC, SLC, IDC circuits will result in a ____ signal.
Trouble.