F/A 1-8 Flashcards
What are the 3 types of Fire Alarm Circuits?
SLC, NAC, and IDC.
What does NAC stand for?
Notification Appliance Circuit.
What does SLC stand for?
Signaling Line Circuit.
What does IDC stand for?
Initiating Device Circuit.
Combustible items found in a protected space are often referred to as ______?
Fuels.
According to NFPA data, structure fires occur approximately every ____ seconds in the US.
24
What mainly contributes to fire alarm system reliability?
Quality of Installation.
The first heat detector used _______ technology.
Fusible Link.
When did ADA become law?
1992
What do Supervisory Signals indicate?
An off-normal condition of a suppression system.
Door unlocking is an example of?
An emergency control function.
Codes Specify?
When and Where.
Standards Specify?
How.
Local AHJ’s can change national codes by?
Adoption.
Loss of AC power is indicated by what type of signal?
A Trouble.
What is a “Manual Fire Alarm Box” also known as?
A pull-station.
Water level switches are a _____ initiating device.
Supervisory.
What type of device directly senses flames?
Radiant Energy Sensing.
Which of the following is a supervisory signal-initiating device?
a. Manual fire alarm box
b. Room temperature switch
c. Spark/ember detector
d. Vane-type flow switch
b. Room Temperature Switch
Vane (or ‘Paddle’) type switches initiate what type of signal?
Alarm.
Ionization-type smoke detectors use ______ as a means of detecting smoke particles.
Americium 241
The most appropriate type of detection for a smoldering fire is?
A photoelectric-type smoke detector.
Ionization type smokes are ideal for detecting smoke particles of what size?
Smaller than one micron.
What type of smoke detector works best in large, open areas?
Projected-Beam type.
The difference in time between the ceiling reaching a certain temperature and the sensing element reaching the same temperature is called ______.
Thermal Lag.
‘Total Coverage’ is defined by _______ but not required by _______.
NFPA-72, Building Codes
T/F: A combustible area that is inaccessible isn’t included in ‘Total Coverage’
False. The area must be made accessible and protected by detectors.
Heat detectors should operate at least _______ above the maximum ambient room temperature.
20 Degrees.
Waterflow switches are permitted to have a time delay of up to ______.
90 Seconds
On smooth + level ceilings, smoke detectors are not permitted to exceed what spacing?
30 Feet
Supervisory Valve ID’s must be made to send a supervisory signal within _____ revolutions of the hand wheel or ______ of the valve travel distance.
2, 1/5
Supervisory Pressure Switches must send a signal when nominal pressure varies by _____.
10 psi
What type of suppression systems are Vane (Paddle) type supervisory switches used with?
Wet Pipe Sprinkler Systems.
Concealed fire detectors more than _____ from the floor must have a remote indicator.
10 Feet
NA’s used outdoors may result in _____ if not listed for such use.
Ground Faults.
The common audible appliance used with an evacuation system would be ______.
Speakers.
T/F: Speakers are an audible textual device.
True.
T/F: Audible and Visible appliances can be wired on the same circuit.
True! Unless its a speaker strobe, then the speakers will have their own circuit.
The Sound Pressure Level (SPL) is always measured using the ______ scale.
A-weighted.
When ambient sound pressure is greater than 105 dBA, _______ are required.
Visible NA’s
Audible notification appliances must be mounted _____ above the finished floor and not less than _____from the ceiling.
90”, 6”
Combination audible/visible notification appliances must be mounted so the entire lens is within _____ above the finished floor.
80-96”
A common example of private-mode signaling is in ______.
Elevator Cars.
A speaker tapped at its highest setting is likely to suffer ____.
Distortion