installing cable in an underground vault/manhole Flashcards
When pulling in cable using a wire-mesh grip with a swivel eye, the pulling tension is usually less than ?
1,000 lbs
One way a duct can be checked for proper diameter and obstructions is to ? through the conduit.
pull a flexible steel mandrel
If a cable is required to make a smooth low-friction 90° turn in a vault, a ? or lip-roller block would be used.
quadrant
Depending on the jurisdiction, underground utility vaults (manholes) more than ? deep are considered to be an enclosed space.
4’
When a blower is used to provide fresh air in an enclosed space such as a manhole, a blower with a capacity of ? cfm or greater is used.
1,000
Historically, about 60% of fatalities involving confined spaces occur when ?
attendants perform a rescue
When ventilating a vault (manhole) with a blower, the space should be ventilated for at least ? before entering.
5 min
When terminating cable in a vault, the bending radius should be at least ? times the cable diameter to prevent damage to the cable.
12
Drop-in anchors for securing cable racks should have a rated pullout working capacity of at least ? lbs.
2,100 lbs
When metallic racks support cables in vaults, the cables are held in support insulators made from ?
high grade porcelain