conduit laying/bending duct banks Flashcards

1
Q

The top of a duct run should be at least ? below the final grade.

A

2’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

On straight pulls, it is rare for the distance between manholes to be greater than ?

A

500’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Normally, the concrete envelope that surrounds an encased duct is ? thick.

A

3”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Manufactured spacers for ducts should be placed approximately every ? to provide adequate support for the duct.

A

5’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

The recommended number of ducts in one 3x3 configuration duct run is ? conductors.

A

9

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Without the use of manufactured bends, the maximum directional change of straight PVC conduit should not be greater than ? .

A

5 degrees

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

PVC conduit is available in lengths ranging from five feet up to ?

A

30’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

The length of a duct run for modern advanced transmission voltage rated cables is limited to ?

A

the amount of cable on the reel

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

When an electric duct system is in a trench shared with vertically stacked telephone or gas utilities, the usual separation is ? between utilities.

A

6”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

If a common trench contains stacked natural gas lines, fiber optic conduits, telephone conduits, and electric cable conduits, the ? lines will be installed at the bottom level.

A

electric

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

The length of a duct run is limited by the ?

A

pull tension required to draw the conductor through the duct.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

When drawing cables through conduits, pull speeds of less than ? are recommended for single conductor pulls.

A

60 feet per minute

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Conduit and natural gas lines must not enter the same manhole.

A

true

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Duct banks should avoid going through or across ?

A

unstable rock

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

The depth of a conduit bank is determined by the ?

A

cable voltage

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Gas lines are never to be run in the same trench with electrical conductors.

A

false