Ilt Flashcards
Setpoint and logic for SI signal on Lo PZR
1870 psig
2/3 logic
Block man <P11
Setpoint and logic for SI signal low steam pressure
675 psig
2/3 logic
Man block on p11
Setpoint and logic for SI signal for high containment pressure
1.54psig
2/3 logic
No blocks
Setpoint and logic for source range monitor
10^5 CPS
Logic 1/2
Block manual >P6
Setpoint and logic for intermediate range monitor hi flux
25% PWR
Logic 1/2
Block Manual >P10
Setpoint and logic for power range monitors Low power
25%
Logic 2/4
Blocked manual >P10
Setpoint and logic PRM HI Flux
105% PWR
Logic 2/4
No block
Setpoint and logic for PRM rate
+5%/2 sec
Logic 2/4
No block
Setpoint and logic for PZR hi pressure
2385psig
Logic 2/4
No blocks
Setpoint and logic for PZR low pressure
1970psig rate sensitive
Logic 2/4
Block is auto at P7
Setpoint and logic for PRZ hi level
92%
Logic 2/3
Block auto @P7
Setpoint and logic for RCS Low flow
<90%
Logic 2/3
Block auto 2LP @ P7 auto 1 LP @ P8
Setpoint and logic for RCP Low voltage
70%
Each RCP has one under voltage. 2/4 logic
Auto 2 LP @P7
Setpoint and logic for RCP Low frequency
57.5 HZ
Each RCP has 1 meter. 2/4 logic
Auto 2 LP @ P7
Will trip all 4 RCPs
Setpoint and logic for SG Lo-Lo level
17%
Logic 2/3 on any 1 SG
No blocks