What is the purpose of a receiver tank?
It stores sub cooled liquid
The sight glass is upstream of (right before) the…..,
Metering device
The king valve is on the outlet of the…
Receiver
Which of these refrigerants is NOT used in refrigerators and freezers?
R-22
R-410A
R-404A
R-134A
R-410A
On a automatic pump-down refrigeration system, which component opens the electrical circuit to the compressor to turn off?
The Low pressure switch
Which can cause the evaporator to freeze up on a reach in commercial refrigerator?
Blocking the airflow with too much product
If a system with a new filter drier has been running for 15 minutes, seeing bubbles in the liquid line sight glass means there is…..,.,,
No subcooling
If the defrost cycle does not intimate on a freezer,the (blank) will continue to attract humidity to it and completely freeze over
Evaporator
If a fuse blows what does that mean?
fuse blows anytime one of your energized circuits make contact with common or ground without first going through a load first
What are three ways to check for a blown fuse?
1.loose wire nut connection
2. One of the wires loose from the terminal
3.one of the wires cut or damaged
With your volt meter how do you test for a blown fuse?
you would want to check continuity or you can check with ohms. If you have a OL reading it’s bad but if you get some type of resistance your fine
If you have a OL reading while checking for ohms on a fuse what does that mean?
You should get some type of reading. If you get a OL reading, you have a bad fuse. Not passing electrical current
Say your indoor blower motor not turning on. And you check from *G to *C and it’s getting 24v where would you check next?
Then with your probes you would want to check from your neutral wire to your fan speed wire on the circuit board. If you get nothing bad board
In defrost mode on a heat pump it’s basically running in normal ac mode at the condenser besides what?
The condensing fan is shut off not rejecting heat causing the outside coil to heat up faster
During defrost mode what is the .W terminal at the condenser doing?
Because you don’t want your heat to drop while it’s defrosting the outside coil it’s going to power 24v back at the control board and turn on your furnace or electrical heat
What two things trigger the heat pump from out of defrost mode?
Until a time commitment is met at 10min (or whatever it’s set too) or temperature sensor is satisfied
What three reasons will cause the evaporator coil to freeze?
- Low indoor airflow
2.low refrigerant charge
3.liquid line restriction
Sometimes technicians will try to raise the low side temperatures by charging the unit up instead of fixing the issue. How would you indicate this?
Very clear indication of this is very high subcooling anywhere from 21 and above
What does the compressor and the condenser fan motor have in common?
The COMMON START AND RUN windings
Where does the START wire go for you condensing fan and your compressor
On the compressor (blue) wire goes to the HERM on the capacitor and for the condensing fan it would be 1or 2 brown wires that goes to FAN on cap or it will have its own capacitor.
Where does the RUN wires go for your compressor and outdoor fan?
They both go to T2 on the contactor usually yellow.
Where would your COMMON wires go to your compressor and outdoor fan?
They would usually go to your T1 terminals on the contactor