Gas - Unit N Flashcards
List two ways of heating domestic hot water.
Instantaneously, as water is needed.
Storage tank, at a constant tempurature.
What is the normal tempurature of domestic hot water?
140°F.
True or False?
Forced-air central furnaces can only blow air in an upward direction into the duct work?
False.
List two types of furnaces which could use duct work in a crawl space.
Down-flow.
Horizontal-flow.
What would constitute a high pressure hot water boiler system?
Over 30 psig.
List three categories of commercial gas ranges.
Heavy duty.
Oriental[][][][]
Restaurant[]]
List two types of infrared heaters.
Low intensity.
High intensity.
What surace tempurature can be reached on a high-intensity heater?
1800°F.
List six items you should check before installing a gas appliance.
Accessibility of appliance.
Electrical supply (current voltage).
Gas supply (correct pressure)[][][][]
Permit (gas, electrical, plumbing)[]]
Suitability of location[][][][][][][][][][][][][]
Water supply and drainage[][][][][][][]]
List five major items you would check after installing a gas-fired appliance.
Air supply for combustion.
Electrical wiring[][][][][][][][][][]
Flues and vents[][][][][][][][][][]
Gas piping[][][][][][][][][][][][][][][]
Water and drainage[][][][][][][]
Is it the general contractor’s responsibility to ensure there is combustion air supply?
No, it is the gasfitters responsibility.
What are the two main things you must do before you light up an appliance?
Purge the piping system of air.
Test for gas leaks[][][][][][][][][][][][]
True or False?
After turning on the main gas valve for the first time, you should immediately head for the appliance and check for leaks.
False (first make sure gas flow stops).
How long must the house pressure be locked in, with no pressure drop showing on the manometer of the pressure guage?
10 minutes.
Natural gas is used to purge a system of air when the pipe size is less than NPS _.
4.
List three locations where air can be purged from a small piping system.
Appliance piping connection.
Pilot tube connection to gas valve.
Readily accessible burner[][][][][][][][]
True or False?
It is okay to allow some gas into the combustion chamber while purging?
False.
How far must the end of the purging hose be from either a building opening or an air intake?
10 feet.
What type of valve must be used at the purging point?
Quarter-turn.
Name the device installed on a domestic hot water tank that will prevent siphoning.
Vacuum relief valve.
Name the device that will protect the hot water tank from high tempuratures and pressures.
Tempurature and pressure relief valve.
If the tempurature selector knob on a domestic hot water tank is turned to the normal setting, what tempurature should the water be heated to?
140°F.
Switch that immediately closes the safety shut off valve when set tempurature exceeded is the definition of?
Energy cut off.
What is the pressure relief setting for a low pressure hot water boiler?
30 psig.
What is the maximum operating pressure for a low pressure steam boiler?
15 psig.
What must be checked on a circulating pump before it can be put into service?
Lubrication.
Rotation[][][]
What is the normal tempurature for an operating aquastat (on a hot water boiler)?
180°F.
What is the normal tempurature for a high-limit aquastat?
200°F.
What are the pressure ranges of an operating pressuretrol (in a low pressure steam boiler)?
On at 1 pisg, Off at 3 psig.
What is the normal high-limit temperature setting for a forced warm-air furnace?
200°F.
Describe the setting on a fan/limit combination control on a forced warm-air furnace.
Fan on 20° above fan off setting Fan off 20° above thermostat setting.
Desrcribe how you can test the operation of a high-limit switch in a forced warm-air furnace.
Disconnect fan motor or fan belt to create high tempurature; ensure high-limit de-energizes gas valve.