What is the maximum fuel pool cleanup strainer delta-p?
3 psid
What is the maximum fuel pool cleanup filter delta-p?
25 psid
If we are placing the PC system on recirc or cleanup, what is our minimum level?
133 feet
What are the high, low, and low-low level alarms in the SFP?
High- 138’ 2”
Low- 137’ 6”
Low-Low- 137’
What happens if the recycle monitor pump trips during a SFP fill?
We need to shut the valve to prevent losing level in the SFP
What concerns do we have when filling the SFP?
At 138’ 3” we could overflow to the tray elevator motor
At 138’ 2” we could flood the in-core instrument tubing
What is the minimum canal level for an irradiated fuel movement inside of containment?
137’ 9”
What are some T.S’s associated with the SFP?
- boron concentration 2150 ppm (4000-4400 ppm as a borated water source)
- 23 feet over irradiated fuel assy’s (137’ 4”)
Where can we get makeup for the SFP from?
LRS RMT
CST
RWT
RMWT
What cools the SFP HX?
NCW
What is the backup source of cooling for the SFP HX?
Essential Cooling Water
For the SFP Cooling and cleanup system where does the suction line and discharge line’s go into the spent fuel pool at?
The suction line takes a suction off of the top part of the SFP while the discharge line delivers water into the bottom of the pool assisting in natural convection cooling.
How far must water level be kept over the top of irradiated fuel in the SFP?
23 feet (137’ 4”)
What is the SFP temperature high and hi-hi alarms in the control room?
High- 125 degrees F
Hi-Hi- 145 degrees F
What are the normal operating conditions for the PC cooling pumps?
50 psig pump discharge pressure
95-100 degrees F SFP Temp
2000 gpm flow rate with one pump running
What are the normal operating conditions for the PC cleanup pumps?
80-85 psig
95-100 degrees F SFP temp
150 gpm flow rate with one pump running
What is the power source for the PC Cooling pumps?
PG
What is the power source for the PC cleanup pumps?
NH
During high heat load periods or refueling; what system can be used to help carry the SFP load?
The Safety injection system through the use of the shutdown heat exchanger
When will the control room get a hi or low pressure alarm for the fuel pool cleanup pump?
HI- 95 psig
Low- 67 psig
When will the control room get a hi or low pressure alarm for the fuel pool cooling pumps?
Hi- 60 psig
Low- 45 psig
What do we want to maintain SFP temperature at?
95-100 degrees F
On our area 3 logs, when do we notify the control room of a higher then normal SFP temperature?
115 degrees F
The N2 bottles for the cask pit/decon area should be reported as being low at what pressure?
300 psig