Foam Pro Flashcards

1
Q

External factors such as ___ will not affect performance or accuracy.

A

hose length, elevation, nozzles, kinks or incoming pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

The system is capable of proportioning foam between ___

A

0.1% to 3.0%.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

0.2% Foam

A

1300 GPM

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

0.5% Foam

A

520 GPM

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

1.0% Foam

A

260 GPM

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

3.0% Foam

A

85 GPM

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

The maximum operating pressure of the Foam Pro Model 2001 Foam System is____.

A

400 psi

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

If the tank is empty, the pump will not run for more than ___.

A

2 minutes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Motor stall protection is provided. In the event that the pump motor will not run or stalls for ____, the display will show “ERR.EL” to indicate that the pump is producing no feedback to the control signal.

A

10 seconds

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

When the fire pump is running, the foam pump cannot pump air efficiently against ____ backpressure.

A

100 to 150 psi

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

In order to pump pressures over___, the Pressure Governor must be operated in the___

A

300 psi / RPM Mode.