a 20 by 20 foot room with a 30 foot high ceiling requires a minimum _______ ceiling mounted strobe
55 CD
Mechanical covers or protection for notification appliances may_______
- Reduce the effectiveness of the appliance
- require de-rating of the appliance
- require reduced spacing of the appliances
combination audible/visible notification appliances must be mounted so the entire lens is between _________ above finished floor
80-96 inches
what are the battery requirements for a fire alarm system battery backup?
24 hours standby plus 5 min of alarm with a 20 percent safety factor.
according to NFPA 72, the lenses of visible notification appliances for non sleeping areas must be mounted _______ above finished floor
80-96 inches
visible notification appliances are required when the ambient sound pressure is greater than?
105 dB
Can a visible notification appliance (strobe) that is listed for wall mounting be used on a ceiling? explain.
no the appliance must be listed for use
will not adequately distribute light
Class C circuitry
WAN / LAN
audible signals in sleeping areas must be
whichever is greater
- 15 dB above average SPL
- 5 dB above max spl sustained 60 seconds or longer
- 75 dB
sound pressure level is always measured using the ______ scale
A-weighted
visible notification appliances used for public mode signaling (for the hearing impaired) must be listed to UL _____>
1971
heat detector distance from ceiling?
4-12 inches
private mode signaling is permitted in _____
elevator cars and rest rooms
Class A circuitry
a pair of both feed and return wires back to panel.
private mode signaling is permitted in _____
elevator cars