Fire Alarm CH 3 Flashcards

1
Q

pressure supervisory switches must indicate _______ from nominal preassure

A

10 psi

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

ionization-type smoke detectors are best suited to detect smoke particles having a size ______ in diameter

A

1 micton

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

ceiling mounted spot type heat detectors are installed so that the edge of the detector is at least _____ from the wall

A

4 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

a smoke detector that has a laser particle counter is best suited for _________.

A

clean rooms

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

for level non smooth ceilings section 17.7.3.2.4.2(1) of NFPA 72 permits the smooth ceiling spacing of spot-type smoke detectors for beans or joists with depth up to _______ of the ceiling height

A

10 percent

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Ionization type smoke detectors use a _______ means of detecting smoke particles

A

americium 241

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

vane or paddle type water flow switches can not be used on what type of system

A

dry pipe

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

a smoke detector is required in each beam pocket where the beam depths are greater than _____ of the ceiling height and the width between beams is equal to or greater than ______ of the ceiling height

A

10 percent

40 percent

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

NFPA 72 permits ______ to be used as a guide for smoke detector spacing on smooth and level ceilings

A

a 30 foot by 30 foot box

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Which type of smoke detector works best in large open areas?

A

projected beam type

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

total coverage is defined by NFPA 72 but _________

A

required by building codes.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

a room temperature switch is a ______________.

A

supervisory signal -initiating device

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

the time difference between the ceiling temperature and the sensing element reaching the same temperature is called?

A

thermal lag

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

on a slopping ceiling beams run up the slope and are 14 inches deep the average ceiling height is 15ft according to NFPA 72 the smoke detector spacing should be _________

A

smooth ceiling spacing

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

total coverage is _______nfpa 72 but ________ by building codes

A

defined, required

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

the most appropriate type of detection for a smoldering fire is a ________.

A

photoelectric or light scattering smoke detector

17
Q

heat detectors should be selected to operate at leas _____ above the maximum expected ambient temperature in the protected space

A

20 degrees F

18
Q

total coverage is __________ but required by building codes

A

defined by NFPA 72

19
Q

waterflow switches are permitted to have a time delay or retard up to _______ seconds

A

90

typically 60 seconds but 90 seconds is amx

20
Q

Water level Switches are a ______ initiating device

A

supervisory

21
Q

total coverage includes inaccessible ________

A

combustible areas

22
Q

the spacing of heat detectors on ceilings with joists is generally reduce by ____________>

A

half in the direction perpendicular to the joists

23
Q

vane or paddle type switches are a ________ initiating device

A

alarm

24
Q

a smoke detector that has a ________ is best suited for clean rooms

A

laser particle counter

25
Q

valve supervisory initiating devices must initiate a supervisory signal within _________ revolutions of the hand wheel or _______ of the travel distance of the valve

A

2

1/5th

26
Q

wall mounted spot type heat detectors are installed so that the top of the detector is _____ from the ceiling

A

4-12 inches

27
Q

supervisory signal-initiating devices indicate a ________.

A

off-normal suppression system

28
Q

what device is used to directly detect flames

A

radiant energy-sensing fire detector

29
Q

rate of rise heat detectors usually operate when the temperature rise is ______ per minute

A

12-15 degrees

30
Q

heat detectors located on a smooth ceiling that is 19 feet in height must be reduced by ________ of their listed spacing

A

64 percent

31
Q

smoke detectors that detect smoke by reflecting light from smoke particles onto a sensor are called ________ smoke detectors

A

light scattering or photo electric