FA5 Flashcards

1
Q

Which article of the NEC covers burglary system wiring?

a. Article 725 b. Article 727
c. Article 760 d. none of the above

A

a. Article 725

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Non-power-limited circuits operate with voltages up to ____.

a. 150 V b. 300 V
c. 600 V d. 750V

A

c. 600 V

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Tables ____ provide limitations for power-limited circuits.

a. 10A and 10B b. 11A and 11B
c. 12A and 12B d. 13A and 13B

A

c. 12A and 12B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Non-power-limited speaker circuits can operate as high as _________

a. 150 V b. 300 V
c. 450 V d. 600 V

A

d. 600 V

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Power-limited wiring requirements are found in Part ___ of Article 760.

a. I b. II
c. III d. IV

A

c. III

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Power-limited equipment is determined to meet the limitations of ______________.

a. NFPA 72 b. the installer
c. the manufacturer d. the testing laboratory

A

c. the manufacturer

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Underground power-limited copper fire alarm circuits that extend outside the building must comply with ____.

a. Parts II, III and IV of Article 800 and Part I of Article 300
b. Parts II, III and IV of Article 300 or Part I of Article 800
c. Parts II, III and IV of Article 800 or Part I of Article 225
d. Parts II, III and IV of Article 300 or Part I of Article 225

A

a. Parts II, III and IV of Article 800 and Part I of Article 300

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Are fire alarm cables permitted to be laid directly on top of suspended ceiling tiles? explain

A

No - they cannot be damaged or lay in the way of normal building use.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

The inside of a conduit installed under a concrete slab at grade level is considered a ___ location.

a. corrosive b. damp
c. dry d. wet

A

d. wet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What cable type is suitable for two hours of direct attack by fire?

A

Circuit integrity (CI) cable and mineral integrity (MI)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Fire alarm circuit survivability is required for ____

a. complete evacuation
b. partial evacuation or relocation
c. both of the above
d. neither of the above

A

c. both of the above

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Circuit integrity (CI) cable can be spliced between the controls and the zone it serves. True or False

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Power-limited circuits may be wired using ____.

a. Chapter 3 wiring methods
b. non-power-limited wiring methods
c. power-limited wiring methods
d. all of the above

A

d. all of the above

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Assuming that there are no approved separations between conductors, which of the following conductors are permitted in the same cable or raceway as power-limited circuit conductors?

a. Class 1 b. Class 2
c. non-power-limited d. none of the above

A

a. Class 2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Type NPLFR cable is permitted to be wired exposed in a plenum space. Explain

A

No - it’s a riser and not allowed by code. You can ues it as NPLF requirements.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Failure to remove conduit burrs usually results in ____

A

ground fault

17
Q

The proper non-power-limited cable for riser use is __

a. FPLP b. FPLR
c. NPLFP d. NPLFR

A

d. NPLFR

18
Q

Describe the conditions under which abandoned fire alarm cables are permitted to remain in a building. Why?

A

If they are tagged for future use - it’s the code

19
Q

Non-power-limited circuits may be wired using what methods?

A

Cables below 7’ must be protected.
Exposed cables must be supported - no more than 18”
Pass through floor or wall must be protected by raceway.
Cable type NPLF, NPLFR, and NPLFP

20
Q

Where non-power-limited wiring is installed exposed, it must be mechanically protected within ___ of the finished floor.

a. 3’ b. 5’
c. 7’ d. 9’

A

c. 7’

21
Q

Fire alarm circuit conductor above a suspended ceiling may use the same support wires that support the ceiling grid. True or False

A

False

22
Q

Fire alarm cables are permitted to be strapped to other conduit. True or False

A

False

23
Q

The location of unit resistances for copper wire is found in ___ of the NEC.

a. Table 3 b. Table 5
c. Table 8 d. Table 12A

A

a. Table 8

24
Q

An 18 AWG uncoated solid copper has a unit resistance of ____ per 1,000 feet.

a. 25.5 Ω b. 7.77 Ω
c. 26.5 Ω d. 8.08 Ω

A

b. 7.77 Ω

25
Q

A circuit that is 1,500 feet from the control unit to the last device will have a loop resistance of ___ when an 18 AWG uncoated solid copper is used.

a. 11.625 Ω b. 23.310 Ω
c. 38.25 Ω d. 76.53 Ω

A

b. 23.310 Ω

26
Q

What is the length of a 16 AWG solid coated copper conductor having a resistance of 23.5 ohms?

a. 4,626’ b. 4,442’
c. 8,884’ d. 9,252’

A

a. 4,626’

27
Q

Firestopping materials are always listed. True or False

A

false

28
Q

A firestopping classification having a minimum F rating of ___ must be used on a two-hour rated firewall to resist the passage of flames.

a. 90 b. 100
c. 110 d. 120

A

d. 120

29
Q

NEC ___ requires electrical penetrations to be firestopped.

a. 320.21 b. 300.21
c. 321.20 d. 321.21

A

b. 300.21

30
Q

A firestopping material that expands when heated is referred to as _____.

a. classified b. dynamic
c. intumescent d. static

A

d. intumescent

31
Q

A cable tray is considered as a ____ penetration.

a. dynamic b. restricted
c. static d. T-rated

A

a. dynamic

32
Q

Which of the following documents can assist in determining if an assembly is two-hour rated?

a. Architectural floor plans
b. National Electrical Code
c. UL Fire Resistance Directory
d. UL 1971

A

UL Fire Resistance Directory