Expected Test Results Flashcards
What results would you expect to see from the measurement of any CPC?
A CPC test should produce a result with a very low resistance, although readings will be higher for longer lengths of cable or CPCs with a low CSA.
What reading would provoke further investigation after determining the resistance of a CPC?
Generally anything above 1Ω
When testing the earth bonding of an installation…
What should the resistance be between the service point and other extraneous-conductive-parts?
0.05Ω or less
When testing the earth bonding of an installation…
What resistance value should the supplementary bonding conductors have?
0.05Ω or less
True or false:
If you are recording results of a final ring circuit, and the highest result is a spur, you should not record this result for your R1+R2 value.
False.
When you are recording the value for the R1+R2 (for use in later tests), you are using the maximum R1+R2 value, as this is the highest value, all other values will be covered by this change in resistance.
What four factors can contribute to a low insulation resistance reading?
- Short-circuit
- Defective insulation
- Ingress of moisture
- Ingress of foreign bodies
Which four factors increase the resistance of conductors?
- Material (Resistivity)
- Area (CSA)
- Length of conductor (Longer = more resistance)
- Temperature (higher temp = higher resistance)
True or false:
An RCD should trip at half of the design current for the circuit/ installation.
False.
If this happens then there is a fault somewhere.