Earthing Arrangements Flashcards
What is the maximum allowed Ze value for a TN-C-S system?
0.35Ω
What is the maximum allowed Ze value for a TN-S system?
0.8Ω
What is the maximum allowed Ze value for a T-T system?
200Ω
What is a PEN Conductor?
In which system would you find it?
What is its function?
- A PEN Conductor is a Protective Earth Neutral Conductor.
- You would exclusively find it in a TC-N-S system
- It provides the neutral and protective earth cable in a TC-N-S system. This is the seperate part of Terra-Combined-Neutral-Seperate
Which of the supply systems has uses the steel wiring of the cable exclusviely for the earth connection?
TN-S system.
The line and the neutral cables are contained within the central core of the SWA cable.
Which of the supply systems uses the general mass of the earth as a return path for earth leakage?
T-T System
What is the figure used to denote the full earth fault loop?
Zₛ
What is the figure used to denote the earth fault loop on the supplier side?
Zₑ
What is the figure used to denote the earth fault loop on the consumer side?
R₁+R₂
True or false:
We want the Zₛ to be as high as possible.
False.
We want the Zₛ to be as low as possible, to ensure that the highest possible amount of current flows to earth as easily as possible, ensuring a rapid disconnection time.
What does TN-C-S stand for?
What does this mean?
Terra Neutral Combined Seperate.
This means that the Earth connection and the Neutral connection enter the property combined, but are then seperated at some point in the installation.
What does PME stand for?
Which system is considered PME?
What does this mean in practice?
PME stands for Protective Multiple Earthing.
TN-C-S system is PME.
This means that the PEN conductor (containing both the supply neutral and earth) is earthed at multiple points on the supply side of the installation.
What is the name of the kind of cable used in a TN-C-S system to house both the Earth and Neutral connections to the supply?
A PEN (combined protective and neutral) or CNE (combined neutral and earth) conductor.