ESW Flashcards
What are the ESW pump auto starts with pump switch in auto?
- Low Header Pressure < 40# (only in Auto)- SI- Load Shed- Opposite unit SI
Will the ESW pump discharge valves automatically open on an auto ESW pump start?
- Yes
Will the ESW pump discharge valves automatically open on a manual pump start?
- Yes
Will the ESW discharge valve auto close on a trip?
- No, they have no automatic closure function
What are the ESW pump trips?
- Load Shed- Overload/Overcurrent- Manual
What are the ESW pump power supplies?
- T11/21D East Pump- T11/21A West Pump
What happens with the ESW to CCW HX outlet valves on a SI?
- ESW to CCW HX outlet valves go to pre-determined throttle position of approx 5000 gpm - CCW Hx outlet valves can be re-positioned with Ctrl Switch after they reach their SI preset position**
What happens with the ESW to CTS HX outlet valves on a SI with Phase B?
- CTS HX outlet valves go to pre-determined throttle position of approx. 2400 gpm (CTS Signal with ICM-305 or 306 Recric Sump Valves open)- Don’t need it until on Recirc sump
Will opening the alt ESW supply to the EDG cause the EDG to be inoperable?
- Yes, it will because if you were to have a single failure, you have the potential to lose both trains of cooling
How is the alt ESW supply to the EDG operated?
- Manually only
Which ESW header has the TDAFP emergency suction supply?
- West Header
Which ESW header has the E MDAFP emergency suction supply?
- East Header
Which ESW header has the W MDAFP emergency suction supply?
- East Header
At what temp will the standby ESW room fan start?
- 90°F
When will the selected ESW room fan start?
- On an ESW pump Start