What are the CW Pump Trips?

A
  • Manual- Overload- instanteous Overcurrent- Undervoltage on the associated RCP Bus
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the De-icing flowpath?

A
  • From a single unit discharge vault (WMO-16 or -26), through the de-ice tunnel and out the middle intake tunnel (WMO-30 is closed).
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What are the indications of icing?

A
  • Circulating Water temperature ≤ 35°F.- Frazzle Ice- > 1 Foot of drawdown in the Forebay not caused by starting a CW Pump- Traveling screens high and/or extreme high differential pressure alarms are annunciating with little or no trash collection in the screen wash trash
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What systems support the CW System?

A
  • Chlorine Injection- Miscellaneous Sealing and Cooling Water- Screen Wash System- Vacuum Priming- 250v DC
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What are the CW System loads?

A
  • NESW- Chlorine Injection (x-tie header)- Miscellaneous SealingCooling Water (x-tie header)- Lawn Sprinkler System (x-tie header)- TACW Heat Exchanger- Main Condensers- Feed Pump Condensers- Radiological Liquid Waste- Turbine Room Sump- Overflow
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What does T.S. 3.7.9, Ultimate Heat Sink, State?

A
  • To meet this condition, the UHS temperature limit of ≤ 88.8°F and the level should not fall below the level necessary for normal unit operation.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

When do the CW outlet valves auto open?

A
  • They auto open with associated CW pump auto start to prevent pump runnout
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Will CW outlet valves auto open on a manual CW pump start?

A
  • No, you must manually open the CW outlet valves on a Manual CW Pump start. This prevents pump runout
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

When do the CW outlet valves auto close?

A
  • Auto close on associated CW pump breaker opening. - Prevents short cycling the system
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

When will a CW pump auto start?

A
  • With the CR Switch in Auto, the CW Pump will auto start on a failure of a running CW Pump. (Running CW control switch in Run with the breaker open.)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What are the CW pump power supplies?

A
  • 1D(2D) / CW Pump #11(21) - 1A(2A) / CW Pump #12(22) - 1B(2B) / CW Pump #13(23) - 2C / CW Pump #24