1
Q
  1. Explain putting the diesel generator in service and how you would adjust vars on the diesel generator as you are loading it.
A
  1. Have plant operator check out generator
  2. Go to diesel generator screen on DCS and start generator, adjust hertz as needed by the frequency adjuster and observe volt meter to confirm it has started
  3. Operator will check generator
  4. Compare phases, make sure they are close
  5. Select G4H breaker and start synch scope, make sure scope is turning slowly in a clockwise direction, compare incoming and running voltages
  6. Close in G4H just before scope reaches midnight
  7. Using load adjuster increase load to 50 KW while adjusting vars to maintain 0 vars
  8. Increase load to 400KW while adjusting vars
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q
  1. What is the purpose of the Inverter?
A

To convert DC to AC, to Supply a clean & reliable source of AC power
to the Woodward controls, plant computers, & boiler control system it also converts AC to clean AC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q
  1. What does the Inverter supply power to?
A

The Woodward controls, plant computers, and boiler control systems

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q
  1. Where does the Inverter get its power?
A

H1- D bus
H2- H bus
H3- D bus

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q
  1. Explain the operating procedure of the inverter.
A

It converts DC power to clean stable AC power

How well did you know this?
1
Not at all
2
3
4
5
Perfectly