Diesel And Inverter Flashcards
1
Q
- Explain putting the diesel generator in service and how you would adjust vars on the diesel generator as you are loading it.
A
- Have plant operator check out generator
- Go to diesel generator screen on DCS and start generator, adjust hertz as needed by the frequency adjuster and observe volt meter to confirm it has started
- Operator will check generator
- Compare phases, make sure they are close
- Select G4H breaker and start synch scope, make sure scope is turning slowly in a clockwise direction, compare incoming and running voltages
- Close in G4H just before scope reaches midnight
- Using load adjuster increase load to 50 KW while adjusting vars to maintain 0 vars
- Increase load to 400KW while adjusting vars
2
Q
- What is the purpose of the Inverter?
A
To convert DC to AC, to Supply a clean & reliable source of AC power
to the Woodward controls, plant computers, & boiler control system it also converts AC to clean AC
3
Q
- What does the Inverter supply power to?
A
The Woodward controls, plant computers, and boiler control systems
4
Q
- Where does the Inverter get its power?
A
H1- D bus
H2- H bus
H3- D bus
5
Q
- Explain the operating procedure of the inverter.
A
It converts DC power to clean stable AC power