DFA Teams Flashcards

1
Q

What does a DFA team consist of?

A

A parent breaker, a normally closed smart switch, a normally open smart switch, and an alternate breaker.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the 90% Rule for picking up load?

A

If the breaker is rated at 480A, then you can pick up 432A. If the breaker is rated at 600A, then you can pick up 540A.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is a 2 team DFA team?

A

They are teams that share a normally open smart switch.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What 10 things will cause a DFA team to go into manual?

A
  1. Parent breaker ground relaying out.
  2. Parent breaker reclosing disabled.
  3. Parent breaker in local.
  4. Parent breaker open for 2 minutes.
  5. Normally closed switch communication fail.
  6. Normally closed switch in local.
  7. Normally closed switch open.
  8. Normally open switch communication fail.
  9. Normally open switch in local.
  10. Normally open switch closed.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What switches are telemetered?

A

KLS, KLC, PDS, PDC & reclosers

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How do you set up clearances with Telemetered Switches?

A
  1. Notify $SEMDIST, if customer team only.
  2. Open telemetered switch via supy or locally. If the switch is part of a team, the team will drop to manual.
  3. Verify open, lock and tag in the field.
  4. Open/verify open bypass switch, lock and tag.
  5. Open jumpers if overhead or decouple device if underground.
  6. Place clearance and abnormal tags in both OMS and EMS.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What needs to be done to a Team Switch inside of a clearance?

A
  1. Notify $SEMDIST
  2. Place team in manual.
  3. Place information tags in both OMS and EMS.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

When should Teams be returned back to auto?

A
  1. When switches return to normal state.
  2. When hold tags are cancelled.
  3. When reclosers are returned after being taken out for trouble shooters or crews.
  4. When clearances are cancelled, and the system is returned to normal.
  5. When switches with problems are repaired and returned to DOC for use.
  6. Any other circumstance causing telemetered switches to go to manual mode including setting up circuits, summer high ground amps, circuit outages, and after load shed, etc.