Device List Flashcards
2
Time Delay Relay
6
Starting Circuit Breaker
21
Distance Relay
25
Sync Check Relay
29
Isolating Contactor
32
Directional Power
27
Undervoltage Relay
40
Field Relay, Loss of Field
41
Field Circuit Breaker
42
Running Circuit Breaker (starter, contactor)
43
Manual Transfer (Control Switch)
46
Reverse or Phase Balance
47
Phase Sequence Relay
49
Thermal Overload Relay, Temperature switch
50
Instantaneous Overcurrent Relay
51
Time Overcurrent Relay
52
AC Circuit Breaker
59
Undervoltage Relay
60
Voltage Balance Relay
61
Current Balance Relay
62
Time Delay Stop or Open
63
Pressure Relay
64
Ground Protective Relay
65
Governor
66
Directional Overcurrent
67N
Directional Ground Relay
70
Rheostat
72
DC Circuit Breaker
74
Alarm Relay
78
Out of Step Relay
81
Frequency Relay
85
Pilot Wire Receiver Relay
86
Lockout Relay
87
Differential Relay
94
Tripping or Trip Free Relay
95
Ground Current Annunciator Relay
71
Level Switch
52Y
Anti-pump Relay
What is the function of the 52Y device?
The Anti-Pump Relay prevents a breaker close when a trip signal is present
52X
Close coil or Spring Release Coil
What is the function of the 52X device?
It electrically closes the breaker by releasing the close latch.
52ST
Shunt Trip Coil
What is the function of the 52ST device?
It electrically trips the breaker
What is the function of the PS1 device in a 12kV Cutler Hammer breaker?
Position Switch 1 initiates anti-pump relay (52Y) to prevent breaker operation during breaker rack in.
What is the function of the PS2 device in a 12kV Cutler Hammer breaker?
Position Switch 2 prevents closing springs from charging during a breaker rack in.
What is the function of the LS1/bb device in a 12kV Cutler Hammer breaker?
The Limit Switch 1 contact opens when closing springs are fully charged to stop the motor.
What is the function of the LS2/aa device in a 12kV Cutler Hammer breaker?
The Limit Switch 2 NO contact remains open to prevent breaker from closing until springs are fully charged.
What is the function of the LS2/bb device in a 12kV Cutler Hammer breaker?
The Limit Switch 2 NC contact initiates the anti-pump relay (52Y) until closing springs are fully charged.