Prevents a closing operation when the breaker is between the Disconnect/Test and Connect positions.
Opens contacts in the 52-LCS to open the close circuit.
Negative Trip Interlock
Backup to the Negative Trip Interlock and provides the same features but operates closer to the connect position.
Redundant Negative Trip Interlock
Prevents racking of a closed breaker.
Will not allow a racking handle access to the hex head jack screw.
Will not allow the lift truck to pick up a closed breaker.
Positive Interlock
Held open by the closing spring discharge interlock which prevents charging the closing spring when the breaker is between the Disconnec/Test and Connect positions in the metalclad
52/CL-MS
Close Latch Monitor Switch
Closed until the closing spring is fully charged
52/SM-LS
Spring Motor Limit Switch
Contacts in the close circuit are held open by the Negative Trip Interlock Roller when the breaker is between the Disconnect/Test and Connect positions
52/LCS
Latch Checking Switch
What two switches are operated by a roller adjacent to the flywheel?
52/SM-LS and 52/CHG
Spring Motor Limit Switch and
52 Charge Switch
What two control schemesdoe the 52/SM-LS serve as a permissive for?
1) Spring Charging Motor Circuit
2) Anti-Pump Relay Circuit
Prevents racking a breaker with the closing spring charged.
Discharges the closing spring if the breaker is between the Disconnect/Test and Connect Positions
Operns the 52/CL-MS to prevent the motor from charging the closing springs
Closing Spring Discharge Interlock