Demand Loads: cooking equip. & appliance demands Flashcards
True or False: A demand factor is the ratio of the maximum demand of the system, or part of a system, to the total connected load of the a system.
True
True or False: The demand load of an electrical appliance is the MINIMUM an appliance may be required at a given time.
False: Maximum required at a given time
What table relates to demand factor for household electric ranges, wall mounted ovens, counter-mounted cooking units and appliance over 1 3/4 kW rating?
Table 220.55
True or False: household electric ranges having a rating of 8.75 kW or more are required to be supplied by at least 40 ampere rated branch circuit.
True
When sizing branch circuits for cooking units, when does the demand factor not apply?
When the units are SINGLE cooking units.
Example ONE wall mounted oven
or ONE counter-mounted cooking unit. The nameplate rating of the appliance applies.
Table 220.55 is separated into four columns.
What does the first column show you?
of appliances
cooking equipment with a rating of less than 3 1/2 kW
cooking equipment with a rating of 3 1/2 to 8 3/4 kW
cooking equipment with a rating of not over 12 kW
The first column shows the number of appliances.
What do you do if a cooking appliance falls under BOTH column A and B?
The demand factors for each column shall be applied for that column and added together
A small residential duplex has 3 kW counter-mounted cooktop and 4kW wall mounted oven installed in each unit. Determine the demand load, in kW to be added to the unground service-entrance conducts for the cooking equipment.
- 7 kW
- 0 kW
- 2 kW
- 5 kW
=9.7 kW
col. A - 3kW +3kW = 6kW x 75% = 4.5 kW
col. B - 4kW +4kW =8kW x 65% = 5.2 kW
=9.7 kW demand
What is the demand load, in kW, for the branch-circuit conductors supplying 8kW residential electric range?
- 0kW
- 4 kW
- 0 kW
- 2 kW
=6.4 kW
8kW x 80% = 6.4 kW demand load
Column C is to be used when applying demand factors for electric ranges of not over 12kW rating
Determine the demand load, in kW, to be added to the ungrounded service entrance conductors for 9.6 kW residential electric range.
- 6 kW
- 0 kW
- 0 kW
- 0 kW
=8.0 kW
Column C of Table 220.55 shows a demand of 8 kW for one range not over 12 kW rating
A ten 10 unit apartment complex is to have a 10 kW electric range installed in each unit. When sizing the unground service-entrance conductors, the total demand load for the multiple ranges is _______.
30 kW
80 kW
25 kW
100 kW
=25 kW
Column C of Table 220.55 shows a demand of 25 kW for 10 ranges of not over 12kW rating.
Note: When applying maximum demand factors of the same rating over 12kW through 27kW, we are to apply note 1 AND column C of the table, which states an increase by 5% for each kW that exceeds 12 kW
What is the branch-circuit demand load, in amperes, for one 16 kW, 240 volt, single phase residential electric range?
33 amperes
50 amperes
40 amperes
67 amperes
=40 amperes
16kW - 12kW = 4kW x 5% = 20% increase in Column C
8 kW x 120% = 9.6 kW demand
I = 9.6 kW x 1000 / 240 volts
9600 / 240 = 40 amperes
When applying demand factor for multiple ranges, all having the same nameplate rating of more than 12kW, but not more than 27 kW, we are able to apply note 1 on table 220.55
A four unit residential town house has a 14kW electric range installed in each unit. What is the demand load for the ranges, in kW, to be added to the ungrounded service-entrance conductors when sizing the service?
- 0 kW
- 8 kW
- 0 kW
- 7 kW
= 18.7 kW
14kW - 12kW= 2 kW x 5% = 10% increase in Column C
col. C demand (4 ranges) = 17kW x 110% = 18.7 kW
When applying maximum demand factors for ranges having UNEQUAL ratings of 8 3/4kW through 27 kW we are to apply note 2 and Column C of Table 220.55
The vocational education department of a high school is to have (3) three electric ranges installed in a classroom; one 10 kW, one 11kW and one 12kW. The ranges are to be supplied by a 208 volt, single phase feeder from a sub panel. What is the demand load, in amperes, on the ungrounded feeder conductors?
58 amperes
67 amperes
136 amperes
142 amperes
=67 amperes
I= 14kW x 1000/ 208 volts
= 14,000/208
=67.3 amperes
When calculating the demand factors for ranges UNEQUAL ratings of 8 3/4 through 27kW, when the nameplate rating of any range less than 12kW, you are to use 12kW as MINIMUM and add the ratings together and divide by the number of ranges to obtain the average
Another classroom in the high school is to install two electric ranges, one 16 kW and one 11kW. Determine the demand load, in amperes, on the 208 volt, single-phase ungrounded feeder conductors.
67 amperes
76 amperes
58 amperes
63 amperes
=58 amperes
12kW (min) + 16kW = 28kW/2(ranges) = 14kW average
14kW-12kW = 2kW x 5% = 10% increase in Col. C.
Col C demand (2 ranges) = 11kW x 110% = 12.1 kW demand
I=12.1 kW x 1000 / 208 volts
= 12,100/208
=58 amperes
True or False: When sizing branch-circuit loads for single branch-circuit supplying a counter-mounted cooking unit and not more than two wall mounted ovens, it is permissible to add the nameplate rating of the appliances together and treat the result as one range.
True